CAIRplus Commissioning and Maintenance
PR-2009-0096-GB • Subject to modifications • R8-10/2015 61
8.3 General considerations
8.3.1 Commissioning of units for indoor installation
DANGER!
Please consider the safety instructions on page 5 and page 55ff when performing
all the described activities!
Complete the following commissioning steps:
Carefully check the entire casing and components for damage and correct fit:
– Doors and service openings
– Seals and gaskets
– Handles and levers
– Connections with foam rubber gaskets
– Sight windows
– Panels
Remove protective film, if applicable.
Remove all transportation/safety locks.
Ensure that there are no loose items inside the unit.
Check that the unit is air tight.
Clean the unit as specified in „Routine cleaning and maintenance“ on page 56.
Damper
blades and
shut-off
dampers (see
to page 80)
Every 6
months
Use a vacuum cleaner to blow off damper blades, never add grease!
Detach the actuator from dampers, check if dampers are moving freely.
Check that the damper actuator moves to its final positions.
Sound
attenuator
(see to
page 80)
Every 6
months
Check the sound attenuator section and sound insulating splitters for dirt, clean
as necessary.
ELECTRICAL HAZARD AND DANGER OF ROTATING UNIT PARTS WITH
SHARP EDGES!
OBSERVE PERSONAL PROTECTION MEASURES
Please consider the safety instructions on page 5 and page 55ff when
performing all the described activities!
Unit part Frequen-
cy
(months)
Action