Commissioning and Maintenance CAIRplus
60 PR-2009-0096-GB • Subject to modifications • R8-10/2015
Cooler with-
out or with
droplet sepa-
rator
(see page 73)
Every 12
months
Check for leak-free condition and possible dirt on the air side.
To ensure frost protection, periodically check the safety devices and take proper
precautions such as draining the equipment or adding antifreeze agents.
Ensure that pipework connections and mountings are securely fixed.
Clean on air side, if necessary (blow through heat exchanger using compressed
air or low pressure water).
Air vent.
Clean coil drip tray and condensate line.
Check trap for proper operation, top up as necessary.
Clean droplet separator with a descaling spray.
Before
winterizati
on
Drain water from the cooling coil before winter.
Evaporator/
condenser
(see page 75)
Every 12
months
Clean and check evaporator/condenser.
Ensure that all refrigeration components (refrigerating machine, direct
evaporator, distribution manifold, refrigerant lines, etc.) are functioning properly.
Heat pipe
(see page 76)
Every 12
months
Clean coil fins.
Clean coil drip tray and condensate line.
Check trap for proper operation, top up as necessary.
If a heat pipe is fitted with a bypass, check air-regulating and shut-off dampers
for proper operation.
Liquid-cou-
pled energy
recovery as-
sembly
(see page 76)
Every 12
months
Complete the same steps specified in "Cooler with/without droplet separator"
(every 12 months).
Plate heat
exchanger
(see page 77)
Every 12
months
Carry out cleaning depending on contamination degree of the plate assembly.
Check bypass damper for proper operation, if required.
Complete wet cleaning only if a tray is installed and available!
Remove oil and fat deposits.
Rotation heat
exchanger
(refer to
page 78)
Every 3
months
Check tension of drive belt, tighten as necessary.
Every 12
months
Clean coil fins – carry out wet cleaning only if a tray is installed! Never use high-
pressure water or steam for cleaning coil fins.
Remove dirt from the section.
Check dampers with energy-recovery system and bypass arrangement for
proper operation.
Check run-around gaskets, adjust as necessary.
Check motor alignment.