EasyManua.ls Logo

Denco CAIRplus - Commissioning and Maintenance of Heater Assemblies

Default Icon
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CAIRplus Commissioning and Maintenance
PR-2009-0096-GB • Subject to modifications • R8-10/2015 71
8.5.7 Maintenance of other filters
DANGER!
Please consider the safety instructions on page 5 and page 55ff when performing
all the described activities!
Refer to the relevant maintenance instructions specified in the supplied documenta-
tion.
8.6 Heater assembly
8.6.1 Commissioning of heater assembly (pumped warm water)
DANGER!
Please consider the safety instructions on page 5 and page 55ff when performing
all the described activities!
Complete the following commissioning steps:
Requirement:
Check supply and return lines for proper connection.
Counterflow mechanism and water inlet on air-discharge side.
Check shut-off devices and other fixtures for proper installation.
Commissioning:
Open provided air vent, if automatic air-venting is not installed.
Charge the coil at the lowest point to prevent air cushions and water hammer.
Slowly open air vent and wait until the coil is flushed with water.
Open air vent completely.
Close air vent; if the levels are different - close air vent gradually until water
displaces air and starts to run out.
Activate primary and secondary pump, check rotation direction and put the coil into
service for ample time.
Set the control valves in reverse position (three-way valves).
Perform a subsequent check by repeated opening of air vent.
Check for leak-free condition.
Operate frost protection in a regulated mode to prevent over-conditioning.
8.6.2 Maintenance of heater assembly (pumped warm water)
DANGER!
Please consider the safety instructions on page 5 and page 55ff when performing
all the described activities!
Carry out the following maintenance steps:
Check for leak-free condition and possible dirt on the air side.
To ensure frost protection, periodically check the safety devices and take proper
precautions such as draining the equipment or adding antifreeze agents.
Ensure that pipework connections and mountings are securely fixed.
If necessary clean the coil on the air side (blow out with compressed air or low-
pressure water).
Air vent.
Electrical hazard and danger of rotating unit parts with sharp edges!
OBSERVE PERSONAL PROTECTION MEASURES
Please consider the safety instructions on page 5 and page 55ff when
performing all the described activities!