A CAUTION
* Never start the engine when the circuit breakers on the generator and load sides are on.
Immediate power feeding can cause an electrical shock accident or a load trouble.
Startup procedure: (Refer to r 5- 3. Starting in the cold weather See p.43 j )
(1) See both the circuit breakers on the generator
side and load side are all OFF.
(2) Turn on the battery switch .
(3) Turn the speed change-over switch on the
control panel to the position of
"START / AUTOMATIC IDLING".
(4) Turn the frequency change-over switch to
either 50Hz or 60Hz.
(5) Turn the single-parallel change-over switch
to single side.
(6) Turn fully the starter switch up to "START".
Immediately after engine starts up, release
the starter key, and it comes to the "RUN"
position automatically. For starting engine again
immediately after shut down, once turn the
switch to the "STOP" position or once turn off
the battery switch, because the protective switch
can be on and make it impossible to restart
START
AUTOMATIC IDLING
LOW HIGH
STOP
STOP
RUN
RUN
_ V - ~ START START