20
2) RUNNING CONFIGURATION AFTER 1° MINUTE DELAY
Assuming that temperatures in both compartments are higher than the set point, both A and
B valves will open to circulate refrigerant in the respective cooling circuits. Opening the
two valves will increase the suction pressure above 0 bar + differential, thus allowing the
pressure switch to close the circuit and engage compressor. Evaporator fan are still OFF,
due to not enough cold coil temperature.