B-2 95-86763.1
For installations in which both the Ci and Li of the intrinsically safe apparatus exceeds 1% of the Co and Lo parameters
of the associated apparatus (excluding the cable), then 50% of Co and Lo parameters are applicable and shall not be
exceeded. The reduced capacitance shall not be greater than 1 µF for Groups IIA and/or IIB, and 600 nF for Group IIC.
Additional Safety Notes:
The following warning is on the product: Warning: Do not open when an explosive gas atmosphere may be present. For
ambient temperature above 60°C use field wiring suitable for maximum ambient temperature. For temperature below
–10°C use suitable field wiring for the lowest temperature.
The ambient temperature range is limited to –55°C to +75°C (for Ex db version) or –50°C to +75°C (for Ex db eb
version).
Cable, bushings and the conduit entries shall be of a type already certified according to relevant ATEX standard, so the
protection principle employed will not be impaired.
Unused conduit entries shall be closed using stop plugs certified for the conditions of use (IP66/IP67 minimum). The stop
plugs should be removable only with the aid of a tool.
The terminal compartment for Eclipse without relays is designed for either an increased safety “e” termination or a
flameproof “d” termination of the supply cable. If a flameproof connection is chosen, then an ATEX certified cable entry
device certified to EN60079 must be used. The Eclipse with relays requires Ex d cable entry devices only.
Shielded cable is required.
The measuring function of the Infrared Gas Detector model PIRECL CO2 version, for explosion protection, according to
Annex II clause 1.5.5, 1.5.6 and 1.5.7 of the Directive 94/9/EC is NOT covered in this EC-Type Examination Certificate.
EN Standards:
EN 50270: 2006
EN 60079-0: 2012 + A11:2013
EN 60079-1: 2014
EN 60079-7: 2015
EN 60079-11: 2012
EN 60529: 1991+ A1 2000
EN 61000-6-4 (Emissions)
EN 61000-6-2 (Immunity)
EN 61010-1:2010
CE: Conforms to:
Low Voltage Directive: 2006/95/EC (until April 19th, 2016)
2014/35/EU (from April 20th, 2016)
EMC Directive: 2004/108/EC (until April 19th, 2016)
2014/30/EU (from April 20th, 2016)
ATEX Directive: 2009/94/6/EEC (until April 19th, 2016)
2014/34/EU (from April 20th, 2016)
Marine Equipment Directive: 96/98/EC, 2015/90/EU