In wet rooms, place the thermostat accord-
ing to local regulation on IP classes. Do not
install the thermostat in small bathrooms
with poor ventilation, nor close to the toi-
let due to the risk of condensed water and
water splash.
Note: A floor sensor enables a more accu-
rate temperature control and is recom-
mended in all floor heating applications
and mandatory under wooden floors to
reduce the risk of over-heating the floor.
Place the floor sensor in a conduit in an appropriate
place where it is not exposed to sunlight or draft
from door openings.
Equally distant and >2cm from two heating cables.
The conduit should be flush with the floor surface -
countersink the conduit if necessary.
Route the conduit to the connection box.
The bending radius of the conduit must be min
50mm.