XR70CX
EN
STANDARD VALUES
Defrost Defrost Defrost
BY AIR BY HOT GAS BY HEATERS
Label Description Range
Default
Level TA
TN TB TN TB
SEt Set point LS - US -5,0
-
10 0 -20 0 -20
Hy Differential (0,1°C÷25,5°C) 2,0 Pr1 2 2 2 2 2
LS Minimum set point (-55,0°C÷SET) -50,0 Pr2 5 -5 -18 5 -18
US Maximum set point (SET÷150,0°C) 110 Pr2 15 5 -25 -5 -25
ot Thermostat probe calibration (-12,0÷12,0°C) 0,0 Pr1 0 0 0 0 0
P2P Evaporator probe presence n – Y Y Pr1 0 0 0 0 0
oE Evaporator probe calibration (-12,0÷12,0°C) 0,0 Pr2 0 0 0 0 0
P3P Third probe presence n – Y n Pr2 n n n n n
o3 Third probe calibration (-12,0÷12,0°C) 0 Pr2 0 0 0 0 0
P4P Fourth probe presence n – Y n Pr2 n n n n n
o4 Fourth probe calibration (-12,0÷12,0°C) 0 Pr2 0 0 0 0 0
odS Outputs delay at start up 0÷255 (min.) 0 Pr2 0 0 0 0 0
AC Anti-short cycle delay 0÷50 (min.) 1 Pr1 2 2 2 2 2
rtr P1-P2 percentage for regulation 0 ÷ 100 (100=P1 , 0=P2) 100 Pr2 100 100 100 100 100
CCt Continuos cycle duration 0÷24.0h 0,0 Pr2 0 0 0 0 0
CCS Set point for continuous cycle (-55.0÷150,0°C) -5 Pr2 0 0 0 0 0
Con Compressor ON time with faulty probe 0÷255 (min.) 15 Pr2 15 15 15 15 15
CoF Compressor OFF time with faulty probe 0÷255 (min.) 30 Pr2 15 15 15 15 15
CF Temperature measurement unit °C - °F °C Pr2 °C °C °C °C °C
rES Resolution dE – in dE Pr1 in in in in in
Lod Probe displayed P1 - P2 - P3 - P4 - SEt - dtr P1 Pr2 P1 P1 P1 P1 P1
rEd
2
X-REP display P1 - P2 - P3 - P4 - SEt - dtr P1 Pr2 P1 P1 P1 P1 P1
dLy Display temperature delay 0 ÷ 20M0 (120) (10 sec.) 0 Pr2 0 0 0 0 0
dtr P1-P2 percentage for disply 1 ÷ 99 50 Pr2 0 0 0 0 0
tdF Defrost type EL – in EL Pr1 EL in in EL EL
dFP Probe selection for defrost termination nP; P1; P2; P3; P4 P2 Pr2 nP P2 P2 P2 P2
dtE Defrost termination temperature (-55÷50.0°C) 8 Pr1 50 20 20 30 30
IdF Interval between defrost cycles 0÷120 (hours) 6 Pr1 4 3 3 3 3
MdF (Maximum) length for defrost 0÷255 (min.) 30 Pr1 30 20 20 30 30
dSd Start defrost delay 0÷255 (min.) 0 Pr2 0 0 0 0 0
dFd Displaying during defrost rt - it - SEt- dEF it Pr2 rt rt rt rt rt
dAd MAX display delay after defrost 0÷255 (min.) 30 Pr2 0 0 0 0 0
Fdt Draining time 0÷255 (min.) 0 Pr2 2 2 2 2 2
dPo First defrost after startup n – Y n Pr2 n n n n n
dAF dAF Defrost delay after fast freezing 0÷24.0h 0,0 Pr2 0 0 0 0 0
FnC Fan operating mode C_n - O_n - C_Y - O_Y o-n Pr1 o-Y o-n o-n o-n o-n
Fnd Fan delay after defrost 0÷255 (min.) 10 Pr1 3 3 3 3 3
FCt
Differential of temperature for forced activation of fans
(0÷50°C) 10 Pr2 0 0 0 0 0
FSt Fan stop temperature (-55÷50.0°C) 2 Pr1 40 40 40 40 40
Fon Fan on time with compressor off 0÷15 (min.) 0 Pr2 0 0 0 0 0
FoF Fan off time with compressor off 0÷15 (min.) 0 Pr2 0 0 0 0 0
FAP Probe selection for fan management nP; P1; P2; P3; P4 P2 Pr2 P1 P2 P2 P2 P2
ALC Temperat. alarms configuration rE – Ab Ab Pr2 rE rE rE rE rE
ALU MAXIMUM temperature alarm 0,0÷50,0°C rel. o ALL÷150°C 110 Pr1 5 5 5 5 5
ALL Minimum temperature alarm 0.0÷50°C rel. o -55÷ALU; -50,0 Pr1 5 5 5 5 5
AFH Differential for temperat. alarm recovery (0,1°C÷25,5°C) 1 Pr2 2 2 2 2 2
ALd Temperature alarm delay 0÷255 (min.) 15 Pr2 0 0 0 0 0
dAo Delay of temperature alarm at start up 0÷24.0h 1,3 Pr2 3 3 4 3 4
AP2 Probe for temperat. alarm of condenser nP; P1; P2; P3; P4 P4 Pr2 nP nP nP nP nP
AL2 Condenser for low temperat. alarm (-55 ÷ 150°C) -40 Pr2 -40 -40 -40 -40 -40
AU2 Condenser for high temperat. alarm (-55 ÷ 150°C) 110 Pr2 150 150 150 150 150
AH2 Differ. for condenser temp. alar. recovery [0,1°C ÷ 25,5°C] 5 Pr2 5 5 5 5 5
Ad2 Condenser temperature alarm delay 0 ÷ 254 (min.) , 255=nU 15 Pr2 15 15 15 15 15
dA2 Delay of cond. temper. alarm at start up 0 ÷ 24H0(144) 13 Pr2 13 13 13 13 13
bLL Compr. off for condenser low temperature alarm
n(0) - Y(1) n Pr2 n n n n n
AC2 Compr. off for condenser high temperature alarm n(0) - Y(1) n Pr2 n n n n n
tbA Alarm relay disabling n=no; y=yes y Pr2 y y y y y
oA3 Fourth relay configuration
ALr = alarm; dEF = do not select it;
ALr Pr2 ALr ALr ALr ALr ALr
Lig = Light; AUS = AUX;
onF = always on; Fan = do not select it;
db = do not select it; dF2 = do not select it
AoP Alarm relay polarity (oA3=ALr) oP; cL cL Pr2 oP CL CL CL CL
i1P Digital input polarity OP – CL cL Pr1 oP Op oP oP oP
i1F Digital input configuration
EAL - bAL - PAL- dor - dEF
dor Pr1 dor dor dor dor dor
AUS - Htr - FAn - ES
did Digital input alarm delay 0÷255 (min.) 15 Pr1 0 60 60 60 60
nPS Number of activation of pressure switch 0÷15 15 Pr2 0 10 10 10 10
OdC Compress and fan status when open door no - FAn - CP - F - C F-c Pr2 F-C F-C F-C F-C F-C
rrd Regulation restart with door open alarm n – Y y Pr2 n n n n n
HES Differential for Energy Saving (-30°C÷30°C) 0 Pr2 0 0 0 0 0
Adr Serrial address 0÷247 1 Pr2 1 1 1 1 1
PbC Kind of probe PtC – ntC ntc Pr1 ntc ntc ntc ntc ntc
onF on/off key enabling nu, oFF; ES nu Pr2 nu nu nu nu nu
dP1 Room probe display (value probe)
-
Pr2
-
-
-
-
-
dP2 Evaporator probe display (value probe)
-
Pr1
-
-
-
-
-
dP3 Third probe display (value probe)
-
Pr1
-
-
-
-
-
dP4 Fourth probe display (value probe)
-
Pr1
-
-
-
-
-
rSE Valore set operativo actual set
-
Pr2
-
-
-
-
-
rEL Software release read only
-
Pr2
-
-
-
-
-
Ptb Map code read only
-
Pr2
-
-
-
-
-