SYMPTOM: PRODUCT COLD BUT NOT COLD ENOUGH
Possible Cause: Compressor Runs But Will Not Cool Product
WHAT TO CHECK SOLUTION
1. Is the temperature control pointer set properly?
YES
1 NO, adjust to desired setting.
2. Domestically, is the voltage supply between 103V and 127V?
YES
2. NO, call the power company.
3. Is the temperature control probe located properly?
YES
3. NO, correct its position.
4. Is the condenser clear of obstruction?
YES
4. NO, clear, clean, or space the vender.
5. Is the evaporator fan free of obstruction?
YES
5. NO, free any obstruction or replace.
6. Is the condenser fan free of obstruction?
YES
6. NO, free any obstruction or replace.
7. Is the evaporator free of ice?
YES
7. NO, defrost and check the following:
gasket seal, port door seal, refrigerant charge.
8. Is the temperature control operational?
YES
8. NO, replace.
9. Is the evaporator fan operational?
YES
9. NO, replace.
10. Is the condenser fan motor operational?
YES
10. NO, replace.
11. Is the refrigerant tubing free of kinks?
YES
11. NO, repair or replace.
12. Is the overload operational?
YES
12. NO, replace.
13. Is the start relay operational?
YES
13. NO, replace.
14. Is there refrigerant in the system?
YES
14. NO, charge system and check for leaks.
15. Consult the Dixie-Narco Factory Service at
1-800-688-9090.
Note: Have the vender model and serial number available.