1101 Series Installation Guide | Digital Monitoring Products 2
INSTALLATION
1
Program the Panel
Refer to the panel programming guide as needed. After completing each of the following steps, press CMD to
advance to the next prompt.
1. At a keypad, enter 6653 (PROG) to access the Programmer Menu.
2. For an 1101E, use the two steps below and then continue to step 3. Otherwise, go to step 3.
▶ Go to SYSTEM OPTIONS. At 1100ENCRYPTION, select ALL to only add encrypted wireless devices
to the system. Select BOTH to allow both encrypted and non‑encrypted wireless devices to be
programmed.
▶ The default passphrase appears at the ENTER PASSPHRASE prompt. Press CMD to keep the default.
Press any select key or area to change the passphrase and enter an 8‑character hexadecimal string
(0‑9, A‑F).
3. At ZONE INFORMATION, enter the wireless zone number you would like to use (must begin in the 500
range when using XR panels).
4. At *UNUSED*, enter the zone name.
5. At ZONE TYPE, press any select key or area and select the zone type.
6. At the NEXT ZN? prompt, select NO.
7. When WIRELESS? displays, select YES.
8. At SERIAL#, enter the eight‑digit device serial number found on device packaging.
9. At CONTACT, select either INTERNAL or EXTERNAL. Use consecutive zone numbers if using both internal
and external contacts.
10. At SUPRVSN TIME, enter a supervision time. Default is 240.
11. At DISARM DISABLE, select NO or YES.
Note: Program the external contact first if using both internal and external contacts with
Disarm/Disable functionality.
12. At the NEXT ZONE prompt, select YES if you are finished programming the zone. Select NO if you would
like to access additional programming options.
13. To save panel programming, go to STOP and press CMD.
2
Install the Battery
Use a 3.0V lithium battery, a DMP Model CR123A battery, or an equivalent model from Sony or Murata. For listed
installations, use either an Energizer® 123battery or a CR123A battery manufactured by Panasonic or Tekcell.
1. Push the button on the end of the transmitter and separate the two halves.
2. Observing polarity, place the battery in the holder and press it into place. Refer to Figure 1during installation.