Instructions for installation, setup and operation - FP9000L-2/4/6/8
Page 14 of 16
Beeper indication The built-in sounder is activated with a discontinuous signal.
Active buttons
button "BUZZER SILENCE". Pressing it leads to:
- disabling the embedded sounder, if it is activated by Fire or Fault;
- activating the built- in sounder, if the panel is in Fire or Fault condition and the
annunciator is disabled by previous pressing the same button.
8.4. DISABLED COMPONENT CONDITION
Panel enters Disabled component condition after a manual operation of disabling a specific
component - a Fire alarm line and/or controllable outputs. The condition is managed through the
information and control screens.
Putting fire lines or controllable outputs in mode Disable is as follows.
1. Level Access 2;
2. Dials the keyboard combination 2222;
3. Led Disable indicator flashes;
4. With button “1” is selected the line or controllable outputs;
5. With button “T is confirmed;
6. Combination 2222 out of the programming mode Disable;
LED indication - light indicators:
- "DISABLE" lights up with a constant yellow light
- "1 2 3 4 5 6 7 8" local line indicator lights up with flashing yellow light.
- "OUTS" flashes when a disabled controllable output.
Beeper indication - not affected by the disabled component condition.
8.5. TEST CONDITION
Panel enters Test condition through manual operation for setting a Fire alarm line in to test. The
condition is managed through screens of Information and control condition. Menu «Test Lines» is fourth
from the main menu.
Putting fire lines in mode Test is as follows.
1. Level Access 2;
2. Dials the keyboard combination 3333;
3. Led Disable indicator “TEST” flashes;
4. With button “1” is selected line;
5. With button “T” is confirmed;
6. Combination 3333 out of the programming mode TEST;
- The line is reset (shuts off its power supply for time 3sec) automatically every 60s.