M4000 Insulation Analyzer User Guide
72A-1230 Rev. F 4-79
July 22, 2005
6. Lift the board out.
7. Remove the replacement Low Voltage Power Supply Board from its
anti-static bag and place it in the Instrument.
8. Reconnect the two cables and reposition any other cables previously
moved as necessary.
9. Replace the Nomex insulator shield.
10. Place the corner brace back into position and replace the four screws to
secure the brace using a Phillips head screwdriver.
11. Replace the top and front covers by reversing the steps in ”Removing the
Front and Top Covers” on page 4-46.