Eskimo Ice Systems
7
Typical Operation Cycle Table
ACTION Delay before Next Step (in seconds) and/or description of action
Initial Start Up Via Breaker 60 Assumed display is in ON position. If not, turn unit on via display.
Pump ON 30
Auger ON 15
Compressor ON
Ice Production
Will continue until sensor reads bin full for 30 sec., fault trip or unit manually
shut down.
BIN FULL 30
Auger Clears
Machine Shuts Down
Ice removed from bin Sensor reads bin not full, calls for ice production.
Pump ON 30
Auger ON 15
Compressor ON
Ice Production
Will continue until sensor reads bin full for 30 sec., fault trip or unit manually
shut down.
FAULT Trip - HPF, LPF,
etc.
30
Clearing Auger
Machine Shuts Down 60
Fault Trip Corrected
Pump ON 30
Auger ON 15
Compressor ON
Ice Production
Will continue until sensor reads bin full for 30 sec., fault trip or unit manually
shut down.
Note:
Above is an example of a typical operation cycle based on default values, cycle will change depending on end
user parameter changes.
Figure 2. Typical Operation Cycle