EasyManua.ls Logo

Dometic RM 2620 - Refrigerator Removal; Periodic Maintenance; Replacing Fuses; Gas Equipment Assembly

Dometic RM 2620
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GAS EQUIPMENT ASSEMBLY
ELECTRIC EQUIPMENT
CARTRIDGE HEATER
The heat necessary for the operation of an absorption
cooling unit is supplied by an electric heater mounted in
a pocket of the boiler system.
These models are equipped with one electrical heater
for 120 volt AC.
To replace the heater proceed as follows:
1. Disconnect the wall plug, and the 12 volt wires.
2. Remove the protection cover see FIG. 1
3. Remove the power module cover see FIG. 1
4. Disconnect the heater leads.
5. With a pair of pliers unfold the lug holding the lid of
the boiler casing and open the lid.
6. Remove some insulation wool so that the heater is
accessible.
7. Turn and lift the heater out of its pocket.
8. Fit the new heater into the pocket.
9. Connect the leads and put on the power module
cover.
10. Reset the insulation and close the lid of the boiler.
11. Replace the protection cover.
FUSES
These models are equipped with 2 fuses, one for the
refrigerator control system and one for AC cartridge
heater. (See table below).
To replace fuse(s) proceed as follows.
1. Disconnect the wall plug, and the 12 volt wires.
2. Remove the power module cover. See FIG. 1.
3. Snap the fuse out of the fuse holder.
4. Fit a new fuse in to the fuse holder.
5. Replace the power module cover.
Control system 3 Amp
AC heater 5 Amp
MAINTENANCE & SERVICE
The user should be aware of service that must be
done on a regular schedule to keep the refrigerator
operating properly. The service should only be
performed by a qualified technician who is familiar
with LP gas systems and refrigerators.
1.
REFRIGERATOR REMOVAL
Before working on the refrigerator, make sure the AC
voltage and DC voltage leads are disconnected. Shut
off the gas supply. Disconnect the gas supply line at
the rear of the refrigerator; (see FIG. 1.). Always use
a back up wrench when loosening and tightening this
connection. Cap the gas supply line, loosen the
screws anchoring the refrigerator to the enclosure
and slide the refrigerator out of the compartment.
When replacing the refrigerator make sure that the
sealing strips are properly positioned.
Replacement is the reverse of removal. Check all gas
connections for leaks.
Refer to section INSTALLATION, page 4 to 7.
2.
PERIODIC MAINTENANCE
To keep your Dometic refrigerator operating efficient-
ly and safely, periodic inspection and cleaning of
several components once or twice a year is recom-
mended.
A. It is important to keep the area at the back of the
refrigerator clean. Check the lower vent, upper vent
and area between these openings for any obstruc-
tions such as bird/insect nests, spider webs, etc.
Clean the coils on the back of the refrigerator. Use a
soft bristled brush to dust off the coils.
It is important to keep the refrigerator area free from
combustible material, gasoline and other flammable
vapors or liquids.
NOTE: The following maintenance is required once or
twice a year, but should only be done by a qualified
serviceman who is familiar with LP gas systems and
refrigerators.
FIG. 9
BURNER JET
INLET FITTING
BURNER MOUNTING SCREWS
THERMOCOUPLE
SPARK
ELECTRODE
PRESSURE TEST PORT
MANUAL SHUT OFF VALVE.
SHOWN IN OPEN POSITION,
USE A QUARTER DOLLAR OR A SLOTTED SCREWDRIVER TO CHANGE POSITION
BURNER TUBE
SOLENOID VALVE
11

Related product manuals