[CHAPTER 7 CAUSE OF FAULT AND REACTION]
7-6 |
DOOCHPUMP
Er-10 (Low Voltage Trip-tLv)
Cause
ㆍOccurred when the power supply voltage is low
ㆍOccurred when the connected load is larger than the power capacity
Reaction
ㆍ Check the drive input voltage.
ㆍ Check the power capacity.
It is possible to check the DC Link voltage on FND display part.
Er-11 (High Voltage Trip-tOv)
Cause
ㆍOccurred when the deceleration time (dr-23) is short comparing to the load inertia.
ㆍOccurred when the drive input voltage is too high.
Reaction
ㆍ Increase the deceleration time (dr-23).
ㆍ Check the driver power supply voltage.
It is possible to check the DC Link voltage on FND display part.
Related Function Function Name Ref. Page
6-18Falling Timedr-23
Er-12 (Motor Overload Operation Trip-tOL)
Cause
ㆍ It generates an alarm and stops operation to protect the motor when the load is above the
overload trip level of the motor rated current (dr-31) and the motor operates for more than
overload trip time (dr-32). That is, if the rated current of the motor is 10[A], the overload trip
level is 120%, and the overload trip time is 5 seconds, the overload operation trip will be
generated when the pump operates above 12[A] of output current for more than 5 seconds.
Reaction
ㆍ Check the rated current of the motor (on the nameplate) and the rated current setting (dr-12).
It is possible to check the DC Link voltage on FND display part.
Related Function Function Name Ref. Page
Motor Capacitydr-10
dr-12 Rated Current of Motor
6-16
6-18
6-19
dr-30 Motor Overload Trip Selection
dr-31 Motor Overload Trip Level
dr-32 Motor Overload Trip Time
*
*
*