ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5
CPS-B1 CPS-B1
99.828.32 1.4/07/2199.828.32 1.4/07/21
8/24 9/24
View motherboard
Rauchabzugszentrale
Smoke Vent Controller
D+H Mechatronic - Germany - +49 40 605 65 0
IP
30
VDS-Nr.:
CPS-B1-xx-0101
IN :
OUT :
Temp. -5°C...40°C
Mains
supply
Group
fault
Control Alarm
Line
fault
Mains
DIP switch
Battery
socket
LED battery
fault
Line
ON-OFF-RESET
Fire recognation element
The control panel has an internal measuring device for monitoring
the internal temperature of the control device. If the internal
temperature is exceeding 72°C (caused by radiant heat of a fire in
immediate vicinity of the mounting place), the entire smoke and heat
vent system will be emergency opened under alarm conditions.
SHEV alarm
Fault
Mains existing
Pictogram explanation
D+H window drive
OK
Control panel O.K.
Fault
Extension
socket
Group
socket
Line
socket
Line extension
socket
(only CPS-B1-5-0101)
LED-Displays
Terminal assignment
No.
Description
Mains supply X1
X1.1
Functional ground
X1.2
Neutral conductor
X1.3
Phase
Extension socket X2
X2.1
Reference potential
X2.2
Output not emergency-supplied potential + (max. 250 mA)
X2.3
Reference potential
X2.4
Output emergency-supplied potential *
X2.5
Isolated output alarm - normally open contact
X2.6
Isolated output - COM
X2.7
Isolated output no alarm / magnet - normally closed contact
X2.8
Isolated output fault - normally closed contact
X2.9
Isolated output - COM
X2.10
Isolated output Control - normally open contact
X2.11
Input, central function, closing of group
X2.12
Reference potential
Ventilation button socket X3
X3.1
Not closed signal output
X3.2
Reference potential
X3.3
Ventilation CLOSE input
X3.4
Ventilation OPEN input
Group socket X4
X4.1
Monitoring
X4.2
Drive output Mot. a
X4.3
Drive output Mot. b
Line socket X5
X5.1
Shield connection for fire detector cable
X5.2
Input fire detector triggering/monitoring
X5.3
Reference potential
X5.4
Input smoke vent button triggering/monitoring
X5.5
Reference potential
X5.6
Output smoke vent button control display
X5.7
Output smoke vent button alarm display
X5.8
Input smoke vent button reset line / close group
X5.9
Output smoke vent button fault display
Line extension socket X6 (only CPS-B1-5-0101)
X6.1
FAS reference potential input
X6.2
FAS alarm input +24V/+48V
X6.3
Additional reset input with pulse function
X6.4
Input/output mutual alarm interlock
X6.5
Reference potential
Battery socket X7
X7.1
Negative lead from battery
X7.2
+24V lead from battery
Service
socket*
Ventilation
button socket
max. 30 V / 0,5 A
OK
Signalling relais
* Service socket
For programming various parameters (Ventilation time, stroke
limitation, invert FAS triggering) via the SCS software
and for resetting the service timer.
** JP1
Jumper for voltage interruption of the group.
When the jumper is removed, the group is switched off,
e.g. to allow maintenance work to be carried out safely.
* If additional loads are connected to the emergency-supplied potential of the CPS-B (X2.4, terminal +), their average
quiescent current consumption in the event of a power failure over 72 hours must not be higher than the value
specified below.
The maximum load capacity of the emergency
potential is 250 mA.
Type
2,2 Ah (Battery-Type 2)
3,4 Ah (Battery-Type 8)
CPS-B1-2.5-0101
16 mA
CPS-B1-5-0101
22 mA
English English