Safety Features
10.1 Emergency Start
The emergency start procedure shortens the self test when the Apollo
must be operational immediately. The emergency start procedure can be
performed up to ten times in succession. After ten cancellations, the system will
not allow another cancellation and a complete self test must be performed.
NOTE: This procedure should only be used in emergency situations!