REGARD
®
3900
Instructions for use
REGARD
®
3900

Other manuals for Dräger Regard 3910

Questions and Answers

  • J
    Jamie RobinsonSep 6, 2025
    Why is the output constant at 1 ± 0.3 mA on my Dräger Controller?
    • B
      Brian CarterSep 6, 2025
      If the output is constant at 1 ± 0.3 mA on your Dräger Controller, it could be due to no signal from the input modules or a faulty output module. Check and connect or repair the ribbon cable. If the issue persists, replace the output module.
  • A
    andrea01Aug 21, 2025
    Why is the display screen blank and all LEDs off on my Dräger Controller?
    • D
      Daniel SantosAug 22, 2025
      If the display screen is blank and all LEDs are off on your Dräger Controller, the issue might stem from a lack of power supply to the controller, a faulty power supply unit, or an internal wiring fault. To address this, first, check and repair the external power supply and wiring. If that doesn't resolve the issue, consider replacing the power supply unit. Finally, inspect and repair the internal power distribution wiring.
  • U
    ugarciaSep 3, 2025
    Why is the Power DC / LED not illuminated but the display screen is on on my Dräger Controller?
    • S
      Sheena MartinSep 4, 2025
      If the Power DC / LED is not illuminated, but the display screen is on for your Dräger Controller, the issue might be a controller supply fault or a faulty display board. Check and repair the external or internal 24 Vdc supply. If the LED still doesn't illuminate, replace the display board.
  • E
    Eduardo GeorgeSep 2, 2025
    What to do if there are no LEDs or data on the display screen for the input module of my Dräger Controller?
    • J
      Joshua LewisSep 2, 2025
      If you have an input module fitted in your Dräger Controller, but no LEDs are illuminated or there is no data on the display screen for the module, it could be due to a ribbon cable fault, an internal wiring fault, a faulty input module, or a faulty display board. You should check and repair or replace the ribbon cable. Also, check and repair the internal power distribution wiring. If the issue persists, replace the input module or the display board.
  • G
    Gregory MillerAug 31, 2025
    Why is the display screen blank on my Dräger Controller?
    • J
      Jennifer WernerSep 1, 2025
      If the display screen on your Dräger Controller is blank, it may be due to no supply to the display board or some other issue. Check and reconnect the ribbon cable to the display board and all modules. If the screen remains blank, replace the display board.
  • A
    Alejandro RodriguezAug 30, 2025
    Why is the Fault (F) LED illuminated for a group of four channels on my Dräger Controller?
    • R
      Ronald LittleAug 30, 2025
      If the Fault (F) LED is illuminated for a group of four channels on the Dräger Controller, it could be due to a transmitter wiring fault, a ribbon cable fault, or a faulty input module. Check and repair the transmitter wiring. If the wiring is not the issue, check and repair or replace the ribbon cable. If the problem persists, replace the input module.
  • L
    loridavisAug 29, 2025
    Why is the gas level on my Dräger Controller different from the remote sensor transmitter?
    • M
      Michael ChurchAug 29, 2025
      If the controller gas level differs from the level displayed at the remote sensor transmitter for your Dräger Controller, it could be due to a transmitter calibration fault, an input channel calibration fault, or an incorrectly set input channel range. Try to recalibrate or set the input channel range the same as the transmitter range.
  • C
    Craig LittleAug 27, 2025
    What to do if Dräger Controller display screen shows: Over-range?
    • R
      Robert RichardAug 27, 2025
      If the display screen on your Dräger Controller displays 'Over-range', the issue likely stems from a short-circuit in the remote sensor transmitter wiring or a fault with the remote sensor transmitter itself. To fix this, you should check and repair the transmitter wiring. If the wiring is not the issue, check and repair the transmitter.
  • C
    christopherandersonAug 26, 2025
    What to do if Dräger Controller display screen shows: Under-range?
    • S
      Sydney CarrAug 26, 2025
      If the display screen of your Dräger Controller shows 'Under-range', it could be due to a faulty transmitter connection, incorrect loop current, or a faulty transmitter. You should check and repair the transmitter wiring. If the wiring is correct, recalibrate the loop current. If the problem persists, replace the transmitter.
  • L
    Lee WebsterAug 25, 2025
    Why is the Fault (F) LED illuminated for a single channel on my Dräger Controller?
    • O
      Omar JamesAug 26, 2025
      If the Fault (F) LED is illuminated for a single channel on your Dräger Controller, it could be due to a transmitter wiring fault, incorrect loop current, a faulty transmitter, or a faulty input module. To resolve this: * Check and repair the transmitter wiring. * Recalibrate the loop current if it's incorrect. * Replace the transmitter if it's faulty. * Replace the input module if necessary.

Summary

Safety-related Information

Product Description

REGARD 3900 Series Features

Overview of the control units, their series components, and primary monitoring capabilities.

System Components

Installation and Commissioning

Mounting and Cable Management

Guidance on unit positioning, mounting, cable entry, and grounding.

Power Supply and Module Installation

Details AC/DC power, module installation, combining, and numbering control modules.

Transmitter and External Connections

Instructions for connecting remote transmitters and other external sources to the system.

Operation Guide

Troubleshooting and Error Resolution

General Fault Diagnosis and Remedies

Lists common faults, causes, and solutions for display and LED issues.

Maintenance and Calibration

Control Unit Configuration and Calibration

Guide to configuring and calibrating the control unit using software or built-in menus.

Technical Specifications

Dräger Regard 3910 Specifications

General IconGeneral
DisplayLCD
Input Voltage24 V DC
WeightApprox. 1.5 kg
Number of sensor inputsUp to 8
Input signal4-20 mA
Power supply24 V DC
TypeGas detection controller
Detection PrincipleElectrochemical, Catalytic, Infrared
Protection RatingIP 65
Operating Temperature-20 to +50 °C
Relay outputs2 relays
Measuring RangesVaries by sensor type
OutputsRelay, 4-20 mA