REGARD
®
3900
Instructions for use
REGARD
®
3900

Questions and Answers

  • D
    Destiny DavisSep 23, 2025
    What does a calibration failure message on my Dräger Controller mean?
    • R
      Rachel MatthewsSep 23, 2025
      If you see a calibration failure message on the screen of your Dräger Controller, it indicates a potential fault with the remote sensor transmitter. Check and repair the transmitter wiring and recalibrate.
  • K
    Kimberly WeissAug 23, 2025
    What to do if I am unable to transfer configuration to or from the Dräger Controller?
    • P
      Phillip CastilloAug 23, 2025
      If you're unable to transfer the configuration to or from the Dräger Controller, this could be due to a lack of power supply to the controller or a fault with the interface unit (RS-232). You should check and repair the external supply and wiring. If the issue persists, check and repair or replace the interface unit.
  • H
    hollycamachoAug 25, 2025
    Why is the Fault (F) LED illuminated for a single channel on my Dräger Controller?
    • D
      Denise MartinezAug 25, 2025
      If the Fault (F) LED is illuminated for a single channel on your Dräger Controller, it could be due to a transmitter wiring fault, incorrect loop current, a faulty transmitter, or a faulty input module. To resolve this: * Check and repair the transmitter wiring. * Recalibrate the loop current if it's incorrect. * Replace the transmitter if it's faulty. * Replace the input module if necessary.
  • G
    Glenn WilliamsAug 26, 2025
    What to do if Dräger Controller display screen shows: Under-range?
    • E
      Eric LeeAug 26, 2025
      If the display screen of your Dräger Controller shows 'Under-range', it could be due to a faulty transmitter connection, incorrect loop current, or a faulty transmitter. You should check and repair the transmitter wiring. If the wiring is correct, recalibrate the loop current. If the problem persists, replace the transmitter.
  • A
    Angela KellerAug 27, 2025
    What to do if Dräger Controller display screen shows: Over-range?
    • E
      ethomasAug 27, 2025
      If the display screen on your Dräger Controller displays 'Over-range', the issue likely stems from a short-circuit in the remote sensor transmitter wiring or a fault with the remote sensor transmitter itself. To fix this, you should check and repair the transmitter wiring. If the wiring is not the issue, check and repair the transmitter.
  • K
    ktaylorSep 18, 2025
    What to do if there is water ingress in my Dräger Controller?
    • C
      Curtis SmithSep 18, 2025
      If there is water ingress in your Dräger Controller, it is probably due to a faulty seal. You should check and repair the cover sealing ring, cable entries, and the front cover information label.
  • S
    Steven RogersSep 15, 2025
    What to do if the LED and display screen test fails on my Dräger Controller?
    • P
      Pamela SteeleSep 15, 2025
      If the LED and display screen test fails on your Dräger Controller, the problem is probably a faulty display board. Replace the display board.
  • T
    tyler05Sep 16, 2025
    Why is the output signal too low on my Dräger Controller?
    • C
      cjonesSep 16, 2025
      If the output signal is too low or will not reach 20 mA on your Dräger Controller, the load resistance may be too high. Reduce the load resistance.
  • H
    hjensenSep 6, 2025
    Why is the output constant at 1 ± 0.3 mA on my Dräger Controller?
    • D
      Dwayne FriedmanSep 6, 2025
      If the output is constant at 1 ± 0.3 mA on your Dräger Controller, it could be due to no signal from the input modules or a faulty output module. Check and connect or repair the ribbon cable. If the issue persists, replace the output module.
  • G
    Gina HendersonSep 3, 2025
    Why is the Power DC / LED not illuminated but the display screen is on on my Dräger Controller?
    • G
      Gregory FlowersSep 3, 2025
      If the Power DC / LED is not illuminated, but the display screen is on for your Dräger Controller, the issue might be a controller supply fault or a faulty display board. Check and repair the external or internal 24 Vdc supply. If the LED still doesn't illuminate, replace the display board.

Summary

Safety Information

Electrical Device Coupling

Guidance on connecting electrical devices safely.

Explosion Hazard Area Use

Regulations and conditions for using the product in explosive atmospheres.

Product Description

System Components

Installation and Commissioning

General Installation Procedures

General safety and procedural instructions for installation and maintenance.

Unit Mounting Guidelines

Guidelines for selecting an installation location and mounting the unit.

Power Supply and Wiring

Overview of AC/DC power supply options and cable entry procedures.

Installing and Combining Modules

General instructions for installing control modules and their combination rules.

Connecting External Devices

Operating the Control Unit

Display Screen Information

Overview of the backlit LCD display and its information display.

Fault Troubleshooting Guide

General Fault Diagnosis and Remedies

Table of common faults, their causes, and suggested remedies for the control unit.

Maintenance and Configuration

Control Unit Configuration and Calibration

Overview of configuring and calibrating the control unit using software and integrated systems.

Technical Specifications

Dräger Regard 3920 Specifications

General IconGeneral
Power Supply24 V DC
TypeGas detection controller
Housing MaterialPolycarbonate
ConnectivityModbus RTU
Dimensions144 x 144 x 110 mm
WeightApprox. 1.5 kg
Input signal4-20 mA
Number of sensor inputsUp to 16
Detection PrincipleElectrochemical, Infrared, Catalytic Bead
Measured Gasescombustible gases
Measurement RangesDependent on sensor
Outputs4-20 mA, Modbus RTU
Operating Temperature-20°C to +50°C