EasyManua.ls Logo

Dräger Regard 3920 - Technical Specifications

Dräger Regard 3920
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
,QVWUXFWLRQVIRUXVH_ REGARD
®
3900 
Technical data
10 Technical data
Versions with operating console (REGARD® 3900 and 3920)
Dimensions 415 x 305 x 175 mm
Weight approx. 5 kg
Material ABS-VO
Degree of protection IP65
Cable entry M20 (qty 30)
All versions
Cable x-section
Max. 2.5 mm
2
Min. 0.5 mm
2
AC input voltage (to energy sup-
ply unit)
Typical: 98 to 253 V AC, 50 to 60 Hz
AC power consumption
2 A energy supply unit
5 A energy supply unit
10 A energy supply unit
Typical: < 0.5 A; max. 0.5 A
Typical: 0.5 A; max. 1 A
Typical: 1 A; max. 2 A
DC input voltage 18 to 30 V DC
DC power consumption at 24 V
Input module:
Relay module:
Output module:
Display:
Interface unit (RS-232):
60 mA with the exception of the transmitter
200 mA
300 mA
170 mA
50 mA
Readings and acoustic signals Readings: LEDs and display
Acoustic signals: Acoustic alarm sounder
Storage temperature -25°C to +70°C
Operating temperature 0 to +55°C
Relative humidity (RH) during
operation and storage
REGARD® 3900/3920:
0 to 100%, non-condensing
REGARD® 3910:
0 to 95%, non-condensing
Warm up time < 40 s
Response time < 2 s
Measurement accuracy Within 1% of the measured value
Module mounts M3
Relays (all modules)
Type Zero potential, single pole changeover relay
Contact material Silver alloy
Nominal switching capacity 5 A 250 V AC; 5 A 30 V DC
Max. switching power 1250 VA; 150 W
Switching voltage Max.: 250 V AC; 100 V DC
Min.: 10 V
Switching current Max.: 5 A
Min.: 100 mA
Output module