DRI-STEEM GTS Humidifier Installation, Operation, and Maintenance Manual • Page 7
Product overview
GTS-DI models
GTS-DI humidifiers burn either natural or propane gas to heat
deionized (DI) or reverse osmosis (RO) fill water into steam for
humidification. GTS-DI models control water level using a float
valve.
GTS-DI models are virtually maintenance-free and require very
little or no downtime.
The GTS-DI model is available for use with deionized or reverse
osmosis water. This unit produces chemical-free steam and reliable,
accurate humidification control.
Notes:
GTS standard water models can be
converted in the field for use with
deionized/reverse osmosis (DI/RO) water.
GTS-DI models can be converted in the
field for use with potable or softened
water.
Damage caused by chloride corrosion is
not covered by your DRI-STEEM
warranty.
Figure 7-1:
GTS-DI (DI/RO water model)
Water supply line
Steam outlet
Drain valve
Overflow outlet
Air gap
Open drain
Float-operated low
water cutoff
Float for water fill valve
Flue connection
Drain piping
Redundant low water
cutoff sensor
OM-1248
Gas valve
Blower
Overview
Note:
Dashed lines indicate supplied by installer