Wiring Chart PC1500RK
Wire Gauge Max. Run Length
(AWG) Keypad to Panel
24 260’ (79m)
22 420’ (127m)
20 660’ (200m)
19 830’ (252m)
18 1050’ (318m)
AUX +
PGM
Z1
COM
DETECTOR
POWER
12VDC
IN
OUT
N.O.
ALM
-
OUT
+
-
IN
+
BLK WHT
RED GRN
LATCHING 4-WIRE
SMOKE DETECTOR
5600Ω 0.5W
END OF LINE
RESISTOR
RM-1 POWER LOOP
SUPERVISORY RELAY
12VDC 35mA MAX.
WHT
ALARM INITIATING
LOOP; RESISTANCE 100Ω
AWG AWG AWG AWG AWG AWG
14 16 18 19 22 24
19 800' 12 450' 7800' 6200' 3000' 1900'
6035m 3794m 2377m 1889m 914m 579m
Figures based on maximum loop resistance of 100 ohms.
Alarm Initiating Loop Wiring Chart
Wire
Gauge
Distance
to EOL
Resistor
Max. Wire Run to E.O.L. Relay
AWG AWG AWG AWG AWG
14 16 18 19 22
4750' 3000' 1880' 1500' 750'
1447m 914m 573m 457m 228m
2375' 1500' 940' 750' 370'
723m 457m 286m 228m 112m
1190' 750' 470' 370' 180'
362m 228m 143m 112m 56m
790' 500' 310' 250' 120'
240m 152m 94m 76m 36m
595' 375' 235' 185' 90'
181m 114m 71m 56m 27m
Current
mA
50
100
200
300
400
Wire run distances are in feet/ meters from the Aux. +/- terminals to the
End-Of-Line Power Supervisory Relay. Figures are based on 12 VDC at
the Aux +/- terminals with a maximum 10% voltage drop at the RM-1
relay.
Fire Zone Power Wiring Chart
Z1
COM Z2
NC
NO
NC
NC
5600Ω 0.5W
END OF LINE
RESISTOR
5600Ω 0.5W
END OF LINE
RESISTOR
EOL RESISTOR
LOOPS USING
NO & NC
DEVICES
EOL RESISTOR
LOOPS USING
NC DEVICES
ONLY
Zone Wiring Chart
Figures based on maximum loop
resistance of 100 ohms.
Wire Gauge Max. Run Length to
(AWG) End-of-Line resistor
24 1900’ (579m)
22 3000’ (914m)
20 4900’ (1493m)
19 6200’ (1889m)
18 7800’ (2377m)
The wiring table gives the wire run length from the control panel
to the keypad for various gauges of wire. Wire run lengths are
based on the maximum current drawn by the keypad. (All lights
ON).
If two wires of the same gauge are paralleled, the run length can
be doubled. eg. If 8 #22 AWG wires are used, 2 red, 2 blk, 2 grn
and 2 yel, the run length would go from 420’ to 840’ (127 to 254
m).
Burglary Zone Wiring
Burglary zone definition, (eg. Delay, Instant, 24 Hr. etc.) is
programmed via the keypad. See the Programming Guide,
Section [11].
Fire Zone Wiring
Any one of the 6 zones may be programmed as a Fire Loop. See
Programming Guide Section [11].
Smoke detectors should be the latching type and have N.O.
alarm initiating contacts. Power wiring from the AUX + /
PGM terminals should be supervised using an RM-1 relay
after the last smoke detector. The RM-1 N.O. contacts
(closed with power applied) should be wired in series with
the alarm initiating end-of-line resistor so that should power
to the detector(s) fail, a fire loop trouble will be initiated.