28
P R O G R A M D E S C R I P T I O N S
Force dialing should be disabled when using Pager format.
When using Pager format, you must program two hex digit E’s at the end of the phone number.
5.7 Communicator – Reporting Codes
Reporting codes must be programmed in order for the panel to report events to the central station.
Reporting codes are two digits and can use hexidecimal digits A through F. To disable a reporting code, program it
as “FF” (default setting) or “00”. All reporting codes are listed and described in Appendix A “Reporting Codes.”
5.7.1 Transmission Delay
The Transmission Delay feature is used to delay reporting of alarms. When a zone is violated and causes an
alarm, the Transmission Delay Timer
will start. When the timer expires, the panel will transmit the programmed
reporting code. If the system is disarmed before the timer expires, the alarm will not be transmitted.
The Transmission Delay zone attribute determines which zones will start the timer.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Transmission Delay Zone Attributes ...................... Section [101]-[132], option [7]
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Transmission Delay Timer ...................................... Section [370]
5.7.2 Low Battery Transmission Delay
When using wireless devices, battery status will be monitored by the panel. If a low battery condition exists,
the panel will indicate a general transmitter low battery trouble. The panel will delay reporting the event for the
number of days programmed as the Low Battery Transmission Delay. This delay provides the user with an
opportunity to change the batteries on the units before the condition is reported to central station. Instruct the
customer on how to change the batteries of wireless devices to gain maximum use of this feature.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Low Battery Transmission Delay ............................ Section [370]
5.7.3 Cross Zone Police Code Reporting
The panel will transmit the Cross Zone Police Code
reporting code, if programmed, when two different
zones are violated within the same armed-to-armed period.
The Burglary Verified Timer, if programmed,
will start when a zone is violated and causes an alarm. If a
second zone is violated before the timer expires, the panel will transmit the Cross Zone Police Code reporting
code. If the timer expires before a second zone is violated, the panel will not send the reporting code, and the
timer will start again. Valid entries for the Burglary Verified timer are 000-255 minutes (000 to disable).
The Double Hit
option allows the Cross Zone Police Code reporting code to be sent when two zone
alarms occur on the same zone. The Burglary Verified timer, if programmed, also applies to the Double
Hit option. Only zones programmed as Interior, Interior Delay, Interior Stay/Away, or Delay Stay/Away are
included in the Double Hit option.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Cross Zone Police Code ........................................ Section [328]
Burglary Verified Timer ........................................... Section [172]
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Double Hit ............................................................... Section [017], option [4]
5.7.4 Delinquency Reporting
The Delinquency feature is used to monitor system activity. When the Delinquency Transmission Delay
timer expires, the panel will transmit the Delinquency reporting code.
If the system is programmed to monitor Activity Delinquency, the timer will be programmed in hours. The
timer will start under the following conditions:
• When the system is armed in the Stay mode
• When the system is disarmed
• When a zone is violated and restored while the system is disarmed/Stay armed (Interior, Interior Delay,
Interior Stay/Away, or Delay Stay/Away zones only).
The activity delinquency timer will be ignored when the system is armed in the Away mode. Zones that
are bypassed in the [✱][1] Bypass menu will not reset the timer.
If the system is programmed to monitor Closing Delinquency, the timer will be programmed in days. The
timer will restart every time the system is disarmed.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Activity/Closing Delinquency.................................. Section [380], option [8]
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Delinquency Transmission Delay ........................... Section [370]
5.7.5 Maintenance
The panel will transmit a Battery Trouble Alarm Reporting Code when the backup battery drops below
11.5 V
DC. The Battery Trouble Restoral Reporting Code will not be transmitted until the battery has been
charged over 12.5 V
DC.
To prevent the panel from transmitting an AC Failure Trouble Alarm Reporting Code during short power
outages the panel will not send the signal unless AC power is lost for the amount of minutes programmed for
the AC Failure Communication Delay. The AC Failure Trouble Restoral Reporting Code will be transmitted