36
Appendix A: Reporting Codes
The following tables contain Contact ID and Automatic SIA for-
mat reporting codes. For more information on reporting code
formats and notes about individual reporting codes, see sections
section 5.8 “Communicator - Reporting Codes” on page 25 and
section 5.7 Communicator - Reporting Formats” on page 23.
Contact ID
The first digit (in parentheses) will automatically be sent by the
control. The second two digits are programmed to indicate spe-
cific information about the signal.
For example, if zone 1 is an entry/exit point, you could program
the event code as [34]. The central station would receive the fol-
lowing:
*BURG - ENTRY/EXIT - 1
where the “1” indicates which zone went into alarm.
SIA Format - Level 2 (Hardcoded)
The SIA communication format used in this product follows the
level 2 specifications of the SIA Digital Communication Standard
- October 1997. This format will send the Account Code along
with its data transmission. The transmission would look similar to
the following at the receiver:
N Ri01 BA 01
N= New Event
Ri01 = Partition /Area Identifier
BA = Burglary Alarm
01 = Zone 1
NOTE: A system event will use the Area Identifier Ri00.
Section # Reporting Code Code Sent When...
Dialer
Direction*
Automatic
Contact ID
Codes
SIA Auto Rep
Codes**
[320]-[323] Zone Alarms zone goes into alarm A/R (1) 3A See Table 3
[324]-[327] Zone Restorals alarm condition has been restored A/R (1) 3A
[328] Duress Alarm duress code entered at keypad A/R (1) 21 HA-00
[328] Opening After Alarm system disarmed with alarm in memory A/R (4) A6 OR-00
[328] Recent Closing alarm occurs within two minutes of system arming A/R (4) 59 CR-00
[328] Zone Expander Supervisory
Alarm/Rest.
panel loses/restores supervisory transmission over the Key-
bus from zone expansion modules, or keypads with zone
inputs
A/R (1) 43 UA-00/UH-00
[328] Cross Zone (Police Code)
Alarm
two zones on the same partition go into alarm during any
given armed-to-armed period (incl. 24Hr zones)
A/R (1) 4A BV-00
[329] [F] Key Alarm/Rest. Keypad fire alarm (alarm and restore rep. codes sent
together)
A/R (1) 15 FA-00/FH-00
[329] [A] Key Alarm/Rest. Keypad auxiliary alarm (alarm and restore rep. codes sent
together)
A/R (1) AA MA-00/MH-00
[329] [P] Key Alarm/Rest. Keypad panic alarm (alarm and restore rep. codes sent
together)
A/R (1) 2A PA-00/PH-00
[330]-[337] Zone Tamper/Restoral zone is tampered / tamper condition restored T/R (1) 44 TA-ZZ/TR-ZZ
[338] General System Tamper/
Rest.
enrolled module with tamper inputs has a tamper alarm/all
module tampers restored
T/R (1) 45 TA-00/TR-00
[338] Keypad Lockout maximum number of incorrect access codes has been
entered at a keypad
T/R (4) 21 JA-00
[339-341] Closings system armed (user 01-34, 40-42 indicated) O/C (4) A2 CL-UU
[341] Partial Closing one or more zones bypassed when system armed O/C (4) 7A CG-ZZ
[341] Special Closing Closing (arming) using one of the following methods: quick
arm, auto arm, keyswitch, function key, maintenance code,
DLS software, wireless key
O/C (4) AA CL-00
[341] Late to Close whenever the auto-arm prealert sounds (if the Late to Close
option is enabled)
O/C (4) A4 CI-00
[342-344] Openings system disarmed (user 01-34, 40-42 indicated) O/C (4) A2 OP-UU
[344] Auto Arm Cancellation auto arm cancelled O/C (4) A5 CE-00
[344] Special Opening Opening (disarming) using one of the following methods:
keyswitch, maintenance code, DLS software, wireless key
O/C (4) AA OP-00
[345]-[346] Battery Trouble/Rest. PC5020 battery is low/battery restored MA/R (3) A2 YT-00/YR-00
* A/R = alarms/restorals; T/R = tampers/restorals; O/C = openings/closings; MA/R = miscellaneous alarms/restorals; T = test transmissions
** UU = user number (user01-42); ZZ = zone number (01-64)