EasyManua.ls Logo

Dungs DMV 11 eco Series User Manual

Dungs DMV 11 eco Series
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
44 .บรมราชชนนี 70 .บรมราชชนนี ศาลาธรรมสพน์ ทวีวัฒนา ทม. 10170.
website: https://www.add-furnace.com/ โทร: 02-888-3472
Line ID: @add11 Wechat ID: add0883001122
Betriebs- und Montage-
anleitung
Doppelmagnetventil
Typ DMV.../11 eco
Typ DMV-D.../11 eco
Typ DMV-DLE.../11 eco
Nennweiten
Rp 2 (DN 50)
DN 65 - 125
Einbaulage
Installation position
Position de montage
Posizione de montaggio
Operation and assembly
instructions
Double solenoid valve
Type DMV.../11 eco
Type DMV-D.../11 eco
Type DMV-DLE.../11 eco
Nominal widths
Rp 2 (DN 50)
DN 65 - 125
Notice d'emploi et de mon-
tage
Electrovanne double
Type DMV.../11 eco
Type DMV-D.../11 eco
Type DMV-DLE.../11 eco
Diamètre nominaux
Rp 2 (DN 50)
DN 65 - 125
Elektrischer Anschluß
Electrical connection
Raccordement électrique
Allacciamento elettrico
IEC 730-1 (VDE 0631 T1)
Istruzioni di esercizio di
montaggio
Valvole doppie
Tipo DMV.../11 eco
Tipo DMV-D.../11 eco
Tipo DMV-DLE.../11 eco
Diametri nominali
Rp 2 (DN 50)
DN 65 - 125
Erdung nach örtlichen Vorschriften
Grounding acc. local regulations
Mise à la terre selon normes locales
Messa a terra secondo prescrizioni locali
AC
DC
Max. Betriebsdruck
Max. operating pressure
Pression de service maxi.
Max. pressione di esercizio
p
max.
= 500 mbar (50 kPa)
V1+V2 Klasse A, Gruppe 2
V1+V2 Class A, Group 2
V1+V2 Class. A, Groupe 2
V1+V2 Class A, Gruppo 2
nach / acc. / selon / la norme
EN 161
U
n
~(AC) 230 V
oder/or/ou/o ~(AC) 110 V
=(DC) 24 V
Einschaltdauer/Switch-on duration/
Dureé de mise sous tension/ Durata
inserzione 100 %
Umgebungstemperatur
Ambient temperature
Température ambiante
Temperatura ambiente
-15 °C … +60 °C (Standard)
0 °C … +60 °C (Viton)
Schutzart
Degree of protection
Protection
Protezione
IP 54 nach / acc. / selon / la norme
IEC 529 (DIN EN 60 529)
Familie 1 + 2 + 3
Family 1 + 2 + 3
Familie 1 + 2 + 3
Famiglia 1 + 2 + 3
Buntmetallfrei, geeignet r Gase bis
max. 0,1 vol. % H2 S trocken.
It does not contain any non-fer-
rous metals, suitable for gases of
up to max. 0.1 vol.% H
2
S, dry.
En alliages non-cuivreux, convient
aux gaz jusqu’à max. 0,1 % en vol.
d’H
2
S sec.
Esso è esente da metalli non ferrosi
ed è adatto per gas fino ad unvolume
max.% di 0,1 H
2
S.
1 … 12
[mbar]
EN 161
[ V ]
0
-15
+60
°C
M/CD Edition 02.15 Nr. 251 419
Question and Answer IconNeed help?

Do you have a question about the Dungs DMV 11 eco Series and is the answer not in the manual?

Dungs DMV 11 eco Series Specifications

General IconGeneral
CategoryControl Unit
ApprovalsEN 161
Protection ClassIP 54
TypeDMV 11 eco
Pressure500 mbar (7.25 psi)
Gas TypesNatural gas, LPG
Valve ClassClass A
Operating Voltage24 V DC
Operating Temperature-20°C to +60°C
Housing MaterialAluminum
Weight2.5 kg

Summary

Operation and Assembly Instructions

Installation and Safety Precautions

General Installation Guidelines

Step-by-step instructions for installing the valve, including tightening screws and testing.

Main Flow Adjustment

Procedure for Setting Main Flow

Step-by-step guide to adjust the main flow rate using screw A.

Component Replacement and Adjustment

Solenoid Replacement Procedure

Flow Rate Diagrams and Gas Properties

Flow Rate Characteristics

Diagrams showing flow rate vs. pressure drop for various valve types and gas conditions.

General Safety and Operational Guidelines

Safe Working Practices

Emphasizes specialist work, avoiding direct contact, and never working with live gas or power.

Installation, Testing, and Adjustment Precautions

Covers proper adjustment, part replacement, pipeline testing, and following manufacturer instructions.

Regulatory Compliance and Component Lifespan

DUNGS Component Replacement Schedule

Recommends replacement intervals for safety-relevant components based on usage.