EasyManua.ls Logo

dymax UVCS 2.0 - Setting Adjustments; Adjusting Conveyor Blower Speed

dymax UVCS 2.0
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Dymax UVCS 2.0 Light-Curing Conveyor User Guide
Setting Adjustments
Adjusting Conveyor Blower Speed
The Blower controls the amount of cooling air provided to the Lamp Assemblies to keep them at proper
operating temperatures. A small percentage of the cooling air is also diverted downward through the
Conveyor Belt. This air flow provides a small hold-down force to keep light objects from moving while traveling
on the belt. The Exhaust Blower speed is set at the factory during final system testing for the Conveyor model
ordered.
If adjustment is required, remove the Access Panel from the front of the Exhaust Blower Housing (Figure 14),
unlock the Speed Control Knob (Figure 15), adjust the Exhaust Blower speed setting, and relock the Speed
Control Knob. The range of the Exhaust Blower Speed Control Knob is 0.0 to 0.85 turns. Table 1 shows the
approximate settings for Exhaust Blower speed.
Figure 14. Access Panel
Figure 15. Speed Control Knob
Table 1. Blower-Speed Potentiometer and Lamp-Cradle Height Settings for Optimum Bulb
Cooling
Model Number
Blower-Speed Potentiometer Setting
Height
1 in
3 in
4.5 in
UVCS-F-1-230
0.20
0.40
0.54
UVCS-F-2-230 or UVCS 39
0.45
0.54
0.80