Jbus MODbus Description Display Attribute
Address Address Code
265 264 Input fail safe (“I.F.S”) R
Range:
0 = Down scale burn out (Lo)
1 = Up scale burn out (Hi)
269 268 External contact function (“E.C.”) R
Range:
0 = Enable external contact for manual alarm reset (nr)
1 = Enable external contact for stop on measuresampling (Ho)
270 269 Contact status (“C.S.”) R
Range:
0 = The selected external contact function is performed with contact
open (OP)
1 = The selected external contact function is performed with contact
close (CL)
271 270 Alarm 1 operative mode (“A1”) R
Range:
0 = Low alarm with manual reset (LL)
1 = Low alarm with automatic reset (LA)
2 = High alarm with manual reset (HL)
3 = High alarm with automatic reset (HA)
4 = No alarm 1 (OFF)
272 271 Alarm 1 action (“A1”) R
Range:
0 = Relay energized in alarm condition (dir = direct action)
1 = Relay energized in no alarm condition(rEV = reverse action)
273 272 Alarm 1 Masking Option (“A1”) R
Range:
0 = Masking Option Disabled
1 = Masking Option Enabled
47