70
Upper display: Full scale value.
Lower display: PI.FSV
Range: from 10 to 99950. Changes to this value affect the values for the pressure input low
scale, the alarm set point limits, the set point limits, the set point and the
retransmission limits.
Default value: 10000.
PRESSURE INPUT LOW SCALE VALUE - Group 3
Available: Always.
Upper display: Low scale value.
Lower display: PI.LSV
Range: from ± 25% of Full scale value.
Default value: 0.
PRESSURE INPUT DECIMAL POINT POSITION - Group 3
Available: Always.
Upper display: Full scale value.
Lower display: PI.DP
Range: Use and keys to select the position of the decimal point.
Default value: None.
REMOTE SET POINT INPUT RANGE LOW - Group 3
Available: Only if RI.TYP is different than OFF.
Upper display: Remote set point input range low.
Lower display: RI.Lo
Range: from 0 to PI.FSV.
Default value: 0.
REMOTE SET POINT INPUT RANGE HIGH - Group 3
Available: Only if RI.TYP is different than OFF.
Upper display: Remote set point input range high.
Lower display: RI.HI
Range: from 0 to PI.FSV.
Default value: PI.FSV.
ALARM 1 INPUT CHANNEL LINK - Group 3
Available: Always.
Upper display: Configuration of alarm 1 selection.
Lower display: A1.LNK
Range: OFF, ProC, band, deu. Disabled, process alarm, band alarm, deviation alarm.