CONTROL OUTPUT RANGE LOW - Group 3
Available: Always.
Upper display: Range low for control output (for RPM scaling).
Lower display: CO.LO
Range: from -10000 to CO.HI.
Default value: 0.
CONTROL OUTPUT RANGE HIGH - Group 3
Available: Always.
Upper display: Range high for control output (for RPM scaling).
Lower display: CO.HI
Range: from CO.LO to 10000.
Default value: 100.0
CONTROL OUTPUT DECIMAL POINT POSITION - Group 3
Available: Always.
Upper display: Range high for control output.
Lower display: CO.DP
Range: Use and keys to select the position of the decimal point.
Default value: One decimal digit.
RETRANSMISSION OUTPUT RANGE LOW - Group 3
Available: Only if RO.TYP is different than OFF.
Upper display: Range low for retransmission output.
Lower display: RO.LO
Range: from 0 to PI.FSV
Default value: 0.
RETRANSMISSION OUTPUT RANGE HIGH - Group 3
Available: Only if RO.TYP is different than OFF.
Upper display: Range high for retransmission output.
Lower display: RO.HI
Range: from 0 to PI.FSV
Default value: PI.FSV
SET POINT LIMIT LOW - Group 3
Available: Always.
Upper display: Low limit for set point.
Lower display: SP.LO