COMMUNICATION BAUD RATE - Group 3
Available: Only if SC.ADR is different than OFF.
Upper display: Baud rate.
Lower display: SC.BDR
Range: 600, 1200, 2400, 4800, 9600, 19200.
Default value: 19200.
LOADING DEFAULT DATA - Group 3
Available: Only if access to level C is allowed.
Upper display: OFF
Lower display: DEFLT
Range: Use and keys to switch the upper display from OFF to On 3, then press FUNC
key to load the default data of the parameters belonging to group 1, group 2 and
group 3.
11.4 GROUP 4 PARAMETERS
SHUNT CALIBRATION - Group 4
Available: Always.
Upper display: OFF if shunt calibration disabled, On if shunt calibration enabled.
Lower display: SHUNT
Range: OFF, On.
Default value: On.
SHUNT VALUE - Group 4
Available: Only if SHUNT parameter is On.
Upper display: Shunt value.
Lower display: SHNT.%
Range: From 40.0 to 100.0%
Default value: 80.0%.
PRESSURE INPUT FAIL SAFE - Group 4
Available: Always.
Upper display: Pressure input fail safe condition.
Lower display: PI.IFS
Range: HI, LO.
Default value: High.