EAS Electric ECRTH2 - Parameter Setting Registers; Home Appliance Type and Temperature Limits

EAS Electric ECRTH2
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
54
Register address Description
200(PLC: 40201) Home appliance type
201(PLC: 40202) Temperature upper limit of T1S cooling
202(PLC: 40203) Temperature lower limit of T1S cooling
203(PLC: 40204) Temperature upper limit of T1S heating
204(PLC: 40205) Temperature lower limit of T1S heating
205(PLC: 40206) Temperature upper limit of TS setting
206(PLC: 40207) Temperature lower limit of TS setting
207(PLC: 40208) Temperature upper limit of water heating
208(PLC: 40209) Temperature lower limit of water heating
209(PLC: 40210) PUMP RUNNING TIME
BIT15 Enable water heating
BIT14 Supports water tank electric heater TBH(Read-only)
BIT13 Supports disinfection
BIT12 DHW PUMP, 1: supported; 0: not supported
BIT11 Reserved
BIT10 DHW pump is valid in disinfection mode
BIT9 Enable cooling
BIT8 T1S cooling high/low temperature settings(Read-only)
BIT7 Enable heating
BIT6 T1S heating high/low temperature settings(Read-only)
BIT5 PUMPI silent mode, 1; valid, 0: invalid
BIT4 Supports room temperature Sensor Ta
BIT3 Supports room thermostat
BIT2 Room thermostat
BIT1 Dual Room Thermostat, 0: not supported;1: supported
BIT0 0: room cooling/heating first, 1: water heating first
Lower 8 bits are for zone 1. higher 8 bits are for zone 2
Remarks
The upper 8 bits are the types of home appliances:
Air to water heat pump: 0x07
The middle 4 bits are product codes: 0x1*
The lower 4 bits are sub-type:
R32: 0x*2
DHW PUMP water return running time. It is five minutes by
default and can be adjusted between 5 and 120 min at an interval
of 1 min.
210(PLC: 40211) Parameter setting 1
Lower 8 bits are for zone 1. higher 8 bits are for zone 2
Lower 8 bits are for zone 1. higher 8 bits are for zone 2
Lower 8 bits are for zone 1. higher 8 bits are for zone 2
Protocol value = actual value * 2
Protocol value = actual value * 2
2) Parameter setting
The following register address 200-208 can only use 03H(Read register) function code.Register
address 209 and follows can use 03H, 06H (write single register), 10H (write multiple register).