55
BIT15
ACS(Double water tank control)
1: Yes 0: No (read only)
BIT14 M1M2 is used for AHS control 1: Yes 0: No
BIT13
RT_Ta_PCNEn(enable Temperature Collection Kit) 1:
Yes 0: No
BIT12 Tbt2 sensor is valid 1: Yes 0: No
BIT11 Piping length selection 1: >10m 0: <10m
BIT10 Solar energy input port 1: CN18 0: CN11
BIT9 Solar energy kit enable 1: Yes 0: No
BIT8 Define the port, 0=remote ON/OFF; 1=DHW heater
BIT7 Smart grid, 0=NON; 1=YES
BIT6 Tw2 sensor enable 0: None 1: Yes
BIT5 Cooling high/low temperature setting T1S2 for Zone 2
(read only)
Heating high/low temperature setting T1S2 for Zone 2
(read only)
BIT4
BIT3 Double zone setting is valid
BIT2 Ta sensor position 1: IDU 0: HMI
BIT1 Tbt1 sensor enable1: Yes 0: No
BIT0 IBH/AHS installation position 1: buffer tank 0: pipe
212(PLC: 40213) dT5_On
213(PLC: 40214) dT1S5
214(PLC: 40215) T_Interval_DHW
215(PLC: 40216) T4DHWmax
216(PLC: 40217) T4DHWmin
217(PLC: 40218) t_TBH_delay
218(PLC: 40219) dT5S_TBH_off
219(PLC: 40220) T4_TBH_on
220(PLC: 40221) T5s_DI
211(PLC: 40212) Parameter s etting 2
Default setting: 5°C, range: 0~10°C, setting interval: 1°C
Default setting: 5°C, range: -5~50°C;
Temperature for the disinfection operation, range: 60~70 ° C,
default setting: 65°C
Default setting: 43°C, range: 35~43°C, setting interval: 1°C
Default: -10°C, range: -25~30°C;
Default setting: 30 min, range: 0~240 min, setting interval: 5
min
Default setting: 10°C, range: 1~30°C;
Default setting: 10°C, range: 5~40°C, setting interval: 1°
C
Default setting: 5 min, range: 5~5 min, setting interval: 1 min