EAS Electric ECRTH2 - Parameter Setting Registers (Cont.); Disinfection and Heating;Cooling Parameters

EAS Electric ECRTH2
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56
221(PLC: 40222) t_DI_max
222(PLC: 40223) t_DI_hightemp
223(PLC: 40224) t_interval_C
224(PLC: 40225) dT1SC
225(PLC: 40226) dTSC
226(PLC: 40227) T4cmax
227(PLC: 40228) T4cmin
228(PLC: 40229) t_interval_H
229(PLC: 40230) dT1SH
230(PLC: 40231) dTSH
231(PLC: 40232) T4hmax
232(PLC: 40233) T4hmin
233(PLC: 40234) T4_IBH_on
234(PLC: 40235) dT1_IBH_on
235(PLC: 40236) t_IBH_delay
237(PLC: 40238) T4_AHS_on
238(PLC: 40239) dT1_AHS_on
240(PLC: 40241) t_AHS_delay
Default setting: 2°C, range: 1~10°C, setting interval: 1°C
Default setting: 25°C, range: 20~35°C, setting interval: 1°C
Default setting: -15°C, range: -25-30°C, Setting interval1°C
Default setting: 10°C, range: -5~25°C, setting interval: 1°C
Time interval of compressor start-up in the heating mode; range:
5~5 min, default setting: 5 min
Default setting: 5°C, range: 2-20°C;
Maximum disinfection duration, range: 90~300 min, default
setting: 210 min
Disinfection high temperature duration, range: 5~60 min, default
setting: 15 min
Time interval of compressor start-up in cooling mode; range: 5~5
min, default setting: 5 min
Default setting: 5°C, range: 2~10°C, setting interval: 1°C
Default setting: 2°C, range: 1~10°C, setting interval: 1°C
Default setting: 52°C, range: 35~52°C, setting interval: 1°C
Delay time for enabling the external heater
A
HS, range: 5~120
min;
default setting: 30 min
The temperature difference between the heat pump s leaving
water set temperature (T1S) and the heat,range: 2~20°C;
default setting: 5°C
Ambient temperature for enabling the hydraulic module auxiliary
electric
heating IBH, range: -15~10°C; default setting: -5°C
Temperature return difference for enabling the hydraulic module
auxiliary, range: 2~10°C; default setting: 5°C
Delay time of enabling the hydraulic module auxiliary electric
heating IBH,range: 15~120 min; default setting: 30 min
The trigger ambient temperature for turning on AHS
range: -15~30°C;default setting: -5°C
V.1