EAS Electric ECRTH2 - Parameter Setting Registers (Cont.); Water Heating and Timing Parameters

EAS Electric ECRTH2
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
57
241(PLC: 40242) t_DHWHP_max
242(PLC: 40243) t_DHWHP_restrict
243(PLC: 40244) T4autocmin
244(PLC: 40245) T4autohmax
245(PLC: 40246) T1S_H.A_H
246(PLC: 40247) T5S_H.A_DHW
247(PLC: 40248) PER_START ratio
248(PLC: 40249) TIME_ADJUST
249(PLC: 40250) dTbt2
250(P LC: 40251) IBH1 power
251(PLC: 40252) IBH2 power
252(P LC: 40253) TBH power
253(PLC: 40254 Comfort parameter
254(P LC: 40255) Comfort parameter
255(PLC: 40256) t_DRYUP
256(PLC: 40257) t_HIGHPEAK
257(PLC: 40258) t_DRYD
258(PLC: 40259) T_DRYPEAK
259(PLC: 40260) t_firstFH
260(PLC: 40261) T1S (first floor heating)
Longest duration of water heating by the heat pump, range:
10~600 min, default setting: 90 min;
Duration of limited water heating by the heat pump, range: 10~600
min, default setting: 30 min;
Default setting: 25°C, range: 20~29°C, setting interval: 1°C
Default setting: 17°C, range: 10~17°C, setting interval: 1°C
Default setting: 25°C, range: 20~25°C, setting interval: 1°C
Range0-200, default setting0,unit: 100W
Reserved, wrong address is reported whe n this register is queried
Reserved, wrong address is reported whe n this register is queried
Temperature rise day number, range: 4~15 days, default setting:
8 days
Drying day number, range: 3~7 days, default setting: 5 days
Temperature drop day number, range: 4~15 days, default
setting: 5 days
In the holiday mode, setting of T1 in the water heating mode,
range: 20~25°C, default setting: 25°C
Range10-100, default setting10.Setting interval10
Range1-60 default setting5
Rrange0-50 default setting15
Range0-200, default setting0, unit: 100W
Range0-200, default setting0, unit: 100W
Highest drying temperature, range: 30~55°C, default setting: 45°
C
Running time of floor heating for the first time, default setting: 72
hrs, range: 48-96 hrs
T1S of floor heating for the first time, range: 25~35 ° C, default
setting: 25°C