6Toxin Shield+ | Installation & Service Manual
Setting the Controller
The EasyWater Toxin Shield+ uses an electronic controller to manage the valve head, regeneration
and backwash processes.
When the unit is in the “Service” position (the unit is providing treated water) the display will
alternate showing the current time of day and the days between regeneration. The regeneration
cycle is preset to occur at 12:30 AM every seventh day. The timing and frequency of regeneration
can be modied as required.
Normal duration for the regeneration cycle is approximately 16 minutes.
1) Backwash = 15 minutes. Water ow is reversed inside the unit to lift the lter media, rinsing
contaminants and sediment from the lter bed.
2) Fast Rinse = 1 minute. This packs the bed, readying the system to begin ltering water again.
3) The system then returns to the “Service” position.
Untreated water is available during the regeneration cycle. It is important that no other water
treatment lter regenerates at the same time. Regeneration of multiple lters should be staggered
in two hour increments.
Follow the regeneration schedule instructions. Do not set the regeneration frequency longer than 7
days, as this risks fouling the lter media and can make the unit inoperable over a period of time.