I.B. 32-255-1G
Page 44
Effective 12/02
SYMPTOM INSPECTION AREA PROBABLE DEFECTS
6-11 TROUBLESHOOTING CHART (Continued Next Page)
Fails To Close
Closing Sound Pole Shaft
but no close (Not open fully)
Trip Latch Reset Spring
(Damaged or Missing)
Trip Bar-D Shaft
(Fails to remain reset)
Trip Latch-Hatchet
(Fails to remain reset)
Trip Floor Tripper
(Fails to remain reset)
Close Latch
(Binding)
Close Latch Roller
(Binding)
Trip Circuit Energized
Undesirably Closes
Control Circuit Close Circuit
(CS/C Getting Shorted)
Mechanism Close Release Latch
(Fails to reset)
Close Floor Tripper
(Fails to reset)
Fails To Trip
No Trip Sound Control Circuit Control Power
(Fuse blown or switch off)
Secondary Disconnect
Auxiliary Switch
(a contact not making, poor or burned)
Trip Coil
(Burned or open)
Terminals and Connections
(Poor or burned or open)
Trip Mechanism Trip Clapper
(Jammed)