5. Maintenance
5.2 Battery-module replacement
Safety recommendations
The battery can cause electrocution and high short-circuit currents. The following safety precautions are
required before servicing the battery components:
• remove watches, rings, bracelets and all other metal objects from the hands and arms,
• use tools with an insulated handle.
A
B
A - Remove the center panel.
B - Remove the left-hand side of the front
panel.
C
C - Disconnect the battery module by
separating the two connectors.
D
D - Remove the metal protection cover in
front of the battery (one screw).
E
E - Remove the battery module and replace
it.
Mounting the new battery module
Carry out the above instructions in reverse order.
• To ensure safety and high performance, use only batteries supplied by EATON.
• Take care to firmly press together the two parts of the connector during remounting.