Table 2. Shear bolt stripback dimensions
Length
variable Measurement name Tolerance in. (mm)
Connector code S1 S3 S4 S5
Allen wrench
(mm) 5 8 8 8
Cutbacks in (mm) in (mm) in (mm) in (mm)
A Bushing to cable +/- ¼
(+/- 6.4)
2
(50.8)
2
(50.8)
2
(50.8)
2
(50.8)
B Jacket +/- ¼
(+/- 6.4)
13
(330.2)
13
(330.2)
13
(330.2)
13
(330.2)
C Insulation shield +/- 1/8
(+/- 3.2)
10½
(266.7)
10½
(266.7)
10½
(266.7)
10 ½
(266.7)
D Conductor +/- 1/8
(+/- 3.2)
2¼
(57.2)
2¾
(69.9)
3¼
(82.6)
3 ¾
(95.3)
E Cable adapter check Maximum 7½
(190.5)
7½
(190.5)
7½
(190.5)
7 ½
(190.5)
Table 1. Shear bolt connector
Cable conductor size Shear bolt connector
AWG or kcmil
mm2
Standard sizes
Centering ring &
color Conductor code Catalog numberCompact Compressed Concentric
1/0 1/0 1/0 25
Grey
S1 CDT630SB150
2/0 2/0 2/0 -
3/0 3/0 3/0 -
Black4/0 4/0 4/0 95
250 250 250 120
300 300 300 150 None
350 350 350 185 Black
S3 CDT630SB300500 500 500 240
None
600 550 550 300
700 600 600
400 None S4 CDT630SB400750 750 750
800 800 800
- - 800 -
None S5 CDT900SB500- 900 900 -
1000 1000 1000 500
3
600 A 15 kV and 25 kV class BT-TAP connector system installation instructions MN650004EN May 2021
Catalog data MN650004EN
Effective May 2021
Deadbreak apparatus connectors