Step 7.
Clean insulation
ote:N Do not apply solvent directly to cable.
Clean insulation thoroughly with solvent dampened rag,
wiping from conductor end toward insulation shield.
(Refer to Figure 19.)
Ensure that all traces of conductive residue are re moved.
Step 8.
Lubricate and install cable adapter
Lubricate exposed cable insulation.
Lubricate inside of cable adapter.
Slide small end of cable adapter over cable using twisting
motion until small end is flush with tape marker. (Refer to
Figure 20.)
After sliding the cable adapter into position make sure
that no bulge is present. (Refer to Figure 21.)
Step 9.
Install compression connector
ote:N Refer to the separate installation instructions
supplied with the shear bolt connector.
Wire brush conductor (aluminum only).
Remove protective cap from compression connector.
Insert conductor completely into compression connector
and rotate connector to distribute inhibitor.
ote:N Connector must be fully seated on cable conductor.
Align flats of compression connector and apparatus
bushing for minimum conductor strain.
Make first crimp .5" (13 mm) below shoulder of
compression connector. (Refer to Figure 22.)
Rotate each successive crimp 90º on com pres sion
connector and allow 1/8" (3 mm) between crimps.
Wipe excess inhibitor from connector and adapter
surfaces.
Figure 19. Line illustration of insulation cleaning.
Wiping Direction
Wipe Insulation
Figure 20. Line illustration of insulation cable adapter.
Lubricate Insulation
Lubricate
Cable Adapter
Tape Marker
WARNING
Equipment Damage/Personal Injury. Improperly
positioned cable adapter may result in equipment
damage or personal injury.
Figure 21. Cross sectional view of cable adapter
positioning.
Straight
Straight
Not Straight
Not Straight
Correct Positioning
Cable
Insulation
Cable
Insulation
Shield
Tape
Marker
Incorrect Positioning
Major OD
flared out
bulge
10
600 A 35 kV class BT-TAP connector system installation instructions for MN650003EN February 2015