Step 10.
Check di men sions
Check length from end of com pres sion con nec tor to top
of cable adapter.
Length should be be tween 6.75" and 7.75" (171 - 197
mm). (Re fer to Fig ure 23.)
Figure 22. Line il lus tra tion of crimping area.
Crimping Area
Bushing
Cable Adapter
Tool
Shoulder
Figure 23. Line illustration for dimensional check.
Compression
Connector
6.75 – 7.75"
(171 – 197 mm)
Tape Marker
Cable Adapter
Concentric
Neutral Wires
11
600 A 35 kV class BT-TAP connector system installation instructions MN650003EN February 2015