600 A 35 kV Class T-OP II connector assembly installation instructions
6INSTALLATION INSTRUCTIONS MN650051EN May 2017
HOTSTICK
O & T TOOL
CONCENTRIC
NEUTRAL
WIRES
T-BODY
APPARATUS
BUSHING
600 A
INTERFACES
Figure 16. Line illustration of installing T-OP II T-body
onto apparatus bushing
Option B - Installing t-OP II T-body on apparatus bushing
using a combined O & T/Torque tool
Clean and lubricate mating interfaces of apparatus
bushing and T-Body with lubricant supplied.
Grasp eye of the O & T/Torque tool with a hotstick, pull
eye fully into hotstick.
Using a hotstick, insert the O & T/Torque tool into the
LRTP throat and engage the rotating nut.
While pushing the T-Body onto the apparatus bushing,
turn O & T/Torque tool clockwise to make the threaded
connection, turn until torque head ratchets (20-25 ft.-Ibs.).
An audible click will be heard.
Remove the O & T/Torque tool.
Step 15
Cap the 200 a interface
Clean and lubricate the 200 A interface of the LRTP and
mating apparatus (i.e., Protective Cap, Grounding Elbow
or M.O.V.E. Arrester) with lubricant supplied.
(Refer to Figure 17.)
To cap interface, follow installation instructions supplied
with apparatus used.
200 A PROTECTIVE
CAP
LRTP 200 A
INTERFACE
CLEAN
AND
LUBRICATE
CONCENTRIC
NEUTRAL
WIRES
T-BODY
Figure 17. Line illustration of protective cap installation
Step 16
Ground system
Connect tie-off tabs of the LRTP and T-Body with a strand
of drain wire to the cable concentric neutral wires and/or
to common ground point.
Connect the 200 A apparatus (i.e., Protective Cap,
Grounding Elbow, M.O.V.E. Arrester) drain wire to
common ground.
Connect concentric neutral wires to the common ground
point leaving adequate slack for hotstick operation.
(Refer to Figure 18.)
DRAIN
WIRES
CONCENTRIC
NEUTRAL
WIRES
T-BODY
Figure 18. Line illustration of grounding

Other manuals for Eaton 600 A T-OP II