-2- 
★  The  building  wiring  socket  outlet  (shockproof  socket  outlet)  must 
be easily accessible to close to the UPS. 
★  With  the  installation  of  the  equipment,  the  sum  of  the  leakage 
current  of  the  UPS  and  the  connected  load  does  not  exceed 
3.5mA. 
★  Do  not  block  ventilation  openings  on  the  UPS’s  housing.  Ensure 
the air vents on the front, side and rear of the UPS are not blocked. 
Recommended at least 25cm of space on each side. The air flow 
diagram is shown as below: 
 
 
 
 
 
 
 
 
 
 
 
■ Figure 1.1 The Air Flow Diagram 
★  UPS has provided earthed connector, in the final installed system 
configuration,  equipotential  earth  bonding  to  the  external  UPS 
battery cabinets.   
★  This  UPS  receives  power  from  more  than  one 
source-disconnection of AC source and the DC source is required 
to de-energize this unit before servicing.   
★  An additional circuit breaker or fuse with rating 32A and breaking 
capacity 3kA shall be used between power source and input when 
installation 3K/3K XL model.   
★  An additional circuit breaker or fuse with rating 16A and breaking 
capacity 3kA shall be used between power source and input when 
installation 1K/1KXL/2K/2KXL model.   
1.2 Operation 
★  For safety consideration, do not disconnect the mains cable on the