Page 20
614-20306-00 - 9SX 0-6 KVA EMEA_EN
3. Installation
G - Access to terminal block and cable wiring
1. Access to terminal block: remove the 4 screws of the terminal block cover.
2. Follow instructions in below sections to wire and secure the cables depending on your connection.
• High leakage current:
Earth connection essential before connecting supply.
H - Common input sources connection
This type of connection must be carried out by qualified electrical personnel.
Before carrying out any connection, check that the upstream protection device Input source is open ("O")
(OFF).
Always connect the earthing wire first.
1. Make sure the metal jumper is connected.
2. Insert the Input source cable through the cable.
3. Connect the 3 cables to the Input source terminal block.
4. Insert the Output cable through the cable gland.
5. Connect the 3 cables to the output terminal block
(10 lb in / 1.2 Nm).
6. Put back and secure the terminal block cover with the 4
screws.
7. Tightened the cable glands.