9SX UPS
9SX EBM
Installation
and user manual
Copyright © 2018 EATON
All rights reserved.
614-20306-00_EN
9SX 0-6 KVA EMEA

Questions and Answers

  • T
    teresahaysAug 13, 2025
    What to do if Eaton 9SX1000I UPS shows power overload?
    • C
      Charles ArmstrongAug 13, 2025
      If the Power overload LED is On and the UPS beeps continuously, it means that the power requirements exceed the UPS capacity. To resolve this, remove some of the equipment from the UPS. Note that the UPS continues to operate, but may switch to Bypass mode or shut down if the load increases.
  • J
    Julie SmithAug 16, 2025
    Why is the Eaton 9SX1000I UPS battery mode LED on?
    • J
      Jasmine HawkinsAug 16, 2025
      The Battery mode LED is On with 1 beep every 10 seconds because a utility failure has occurred, and the UPS is now in Battery mode. The UPS is using battery power to keep your equipment running. You should prepare your equipment for shutdown.
  • R
    reidjohnAug 20, 2025
    What to do if my Eaton 9SX1000I UPS doesn't start?
    • R
      Ralph CabreraAug 21, 2025
      If the Eaton UPS doesn't start, there might be several reasons. First, check the input connections to ensure the input source is correctly connected. Second, ensure that the Remote Power Off (RPO) switch is not active, and the RPO connector is properly connected. If the UPS Status menu displays the 'Remote Power Off' notice, inactivate the RPO input.
  • M
    martinrichardAug 25, 2025
    What to do if Eaton 9SX1000I UPS is overheating?
    • M
      Michelle JonesAug 25, 2025
      If the UPS overtemperature LED is On and it beeps every 3 seconds, it indicates that the UPS internal temperature is too high or a fan has failed. If the UPS transferred to Bypass mode, it will return to normal operation when the temperature drops 5 °C below the warning level. If the condition persists, shut down the UPS. Clear vents and remove any heat sources. Allow the UPS to cool. Ensure the airflow around the UPS is not restricted. Restart the UPS.
  • C
    cynthia26Aug 27, 2025
    What to do if Eaton 9SX1000I battery fault LED is on?
    • K
      Katelyn KellyAug 27, 2025
      If the Battery fault LED is On and the UPS beeps continuously, it indicates that the battery test failed due to bad or disconnected batteries, or the battery minimum voltage is reached in ABM® cycling mode. Verify that all batteries are properly connected. Start a new battery test.
  • M
    Michael JamesAug 31, 2025
    Why Eaton 9SX1000I battery low LED is on?
    • A
      awalkerAug 31, 2025
      The Battery low LED is On and the UPS beeps every 3 seconds because the UPS is in Battery mode and the battery is running low. This warning is approximate, and the actual time to shutdown may vary significantly. Depending on the UPS load and number of Extended Battery Modules (EBMs), the 'Battery Low' warning may occur before the batteries reach 20% capacity.
  • E
    Elizabeth ThomasSep 4, 2025
    How to fix Eaton 9SX1000I not providing expected backup time?
    • B
      briancrawfordSep 4, 2025
      If the Eaton UPS isn't providing the expected backup time, it could be that the batteries need charging or service. To address this, apply utility power for 48 hours to charge the batteries.
  • D
    dana53Sep 8, 2025
    What to do if Eaton UPS no battery LED is on?
    • J
      John DavisSep 8, 2025
      If no battery LED is On and the UPS beeps continuously, it means that the batteries are disconnected. Verify that all batteries are properly connected.

Summary

Safety Instructions

Safety of Persons

Guidelines for safe handling and operation of the UPS system by individuals.

Product Safety

Safety guidelines related to the installation and operation of the UPS product itself.

Special Precautions

Specific precautions to be taken during handling and installation of the UPS unit.

Installation

UPS Connection Requirements

Specifies required protective devices and cable cross-sections for UPS installation.

Terminal Block and Cable Wiring

Guides on accessing the terminal block and wiring for UPS connections.

Common Input Sources Connection

Details the procedure for connecting common input power sources to the UPS.

Separate Input Sources Connection

Instructions for connecting separate input power sources to the UPS.

Connecting the EBM

Provides instructions on how to connect the EBM to the UPS.

Interfaces and Communication

Operation

Start-up and Normal Operation

Step-by-step guide for starting up the UPS and ensuring normal operation.

Starting UPS on Battery

Instructions on how to start the UPS using battery power when utility power is absent.

UPS Shutdown

Procedure for safely shutting down the UPS unit.

UPS Maintenance

When to Replace Batteries

Informs about battery lifespan and provides guidance on replacing UPS batteries.

Replacing Batteries

Lists warnings, precautions, and general steps before and during battery replacement.

Replacing Rack Batteries

Step-by-step guide for replacing the internal batteries in rack-mounted UPS units.

Replacing Tower 0-3 KVA Batteries

Step-by-step guide for replacing internal batteries in the Tower 0-3KVA UPS model.

Replacing Tower 5-6 KVA Batteries

Instructions for replacing internal batteries in Tower 5-6KVA UPS models.

Troubleshooting

Typical Alarms and Faults

Provides a chart to identify and resolve common UPS alarms and faults.

Specifications

Eaton 9SX1000I Specifications

General IconGeneral
Power Rating1000 VA / 900 W
Output WaveformPure sine wave
Transfer Time0 ms
Dimensions (HxWxD)5.9 x 8.7 x 16.5 in
Form FactorTower
Humidity0-95% non-condensing
TopologyOnline Double Conversion
Output Frequency50/60 Hz
Communication PortsUSB, RS-232
Interface PortsUSB, RS-232
Management Card SlotYes
Battery TypeSealed, lead-acid
Operating Temperature0 to 40 °C

Related product manuals