9SX UPS
9SX EBM
Installation
and user manual
Copyright © 2018 EATON
All rights reserved.
614-20306-00_EN
9SX 0-6 KVA EMEA

Questions and Answers

  • A
    Ashley WilliamsAug 13, 2025
    What to do if Eaton UPS shows power overload?
    • E
      Eric StevensAug 13, 2025
      If the Power overload LED is On and the UPS beeps continuously, it means that the power requirements exceed the UPS capacity. To resolve this, remove some of the equipment from the UPS. Note that the UPS continues to operate, but may switch to Bypass mode or shut down if the load increases.
  • J
    Jordan FisherAug 17, 2025
    Why is the Eaton 9SX3000IM battery mode LED on?
    • W
      Walter CarrollAug 17, 2025
      The Battery mode LED is On with 1 beep every 10 seconds because a utility failure has occurred, and the UPS is now in Battery mode. The UPS is using battery power to keep your equipment running. You should prepare your equipment for shutdown.
  • D
    Daisy ReyesAug 21, 2025
    What to do if my Eaton 9SX3000IM doesn't start?
    • C
      Cheryl MckeeAug 21, 2025
      If the Eaton UPS doesn't start, there might be several reasons. First, check the input connections to ensure the input source is correctly connected. Second, ensure that the Remote Power Off (RPO) switch is not active, and the RPO connector is properly connected. If the UPS Status menu displays the 'Remote Power Off' notice, inactivate the RPO input.
  • R
    Roger RodriguezAug 25, 2025
    What to do if Eaton 9SX3000IM UPS is overheating?
    • K
      Kevin ArmstrongAug 26, 2025
      If the UPS overtemperature LED is On and it beeps every 3 seconds, it indicates that the UPS internal temperature is too high or a fan has failed. If the UPS transferred to Bypass mode, it will return to normal operation when the temperature drops 5 °C below the warning level. If the condition persists, shut down the UPS. Clear vents and remove any heat sources. Allow the UPS to cool. Ensure the airflow around the UPS is not restricted. Restart the UPS.
  • D
    Daniel JonesAug 28, 2025
    What to do if Eaton UPS battery fault LED is on?
    • D
      David KeyAug 28, 2025
      If the Battery fault LED is On and the UPS beeps continuously, it indicates that the battery test failed due to bad or disconnected batteries, or the battery minimum voltage is reached in ABM® cycling mode. Verify that all batteries are properly connected. Start a new battery test.
  • C
    conwayericaSep 1, 2025
    Why Eaton UPS battery low LED is on?
    • C
      Cory FrazierSep 1, 2025
      The Battery low LED is On and the UPS beeps every 3 seconds because the UPS is in Battery mode and the battery is running low. This warning is approximate, and the actual time to shutdown may vary significantly. Depending on the UPS load and number of Extended Battery Modules (EBMs), the 'Battery Low' warning may occur before the batteries reach 20% capacity.
  • L
    Lindsey SimmonsSep 5, 2025
    How to fix Eaton 9SX3000IM UPS not providing expected backup time?
    • M
      Mark BellSep 5, 2025
      If the Eaton UPS isn't providing the expected backup time, it could be that the batteries need charging or service. To address this, apply utility power for 48 hours to charge the batteries.
  • F
    Frank MillerSep 8, 2025
    What to do if Eaton UPS no battery LED is on?
    • C
      Colleen AndersonSep 9, 2025
      If no battery LED is On and the UPS beeps continuously, it means that the batteries are disconnected. Verify that all batteries are properly connected.

Summary

Safety Instructions and Precautions

Safety of Persons and Product

Details safety precautions for personnel handling the UPS and outlines product safety guidelines.

Special Handling Precautions

Covers handling, installation, and maintenance safety measures for the UPS.

3. UPS Installation Procedures

Equipment Inspection and Preparation

Instructions for checking equipment for damage and preparation before installation.

4. Interfaces and Communication

5. UPS Operation and Settings

UPS Startup, Shutdown, and Modes

Procedures for starting, starting on battery, shutting down, and operating modes.

6. UPS Maintenance

Battery Replacement and Recycling

Information on battery lifespan, replacement procedures, and equipment recycling.

7. Troubleshooting UPS Issues

Alarm and Fault Diagnosis

Diagnosing common UPS alarms and faults, and silencing procedures.

8. Technical Specifications

Eaton 9SX3000IM Specifications

General IconGeneral
Power Rating3000 VA / 2700 W
Output Frequency50/60 Hz
Frequency Range45 - 65 Hz
Typical Recharge Time3 hours
Operating Temperature0 to 40 °C
Battery TypeSealed Lead-Acid (SLA)
Management SoftwareIntelligent Power Manager (IPM)
Output ReceptaclesIEC 320 C13, IEC 320 C19
CommunicationUSB, Serial, Relay
Communication Ports1 USB port, 1 serial port, relay contacts
Operating Humidity0-95% RH, non-condensing
TopologyDouble Conversion Online