9SX UPS
9SX EBM
Installation
and user manual
Copyright © 2018 EATON
All rights reserved.
614-20306-00_EN
9SX 0-6 KVA EMEA

Questions and Answers

  • K
    Kurt LeeAug 14, 2025
    What to do if Eaton UPS shows power overload?
    • D
      Danielle KellyAug 14, 2025
      If the Power overload LED is On and the UPS beeps continuously, it means that the power requirements exceed the UPS capacity. To resolve this, remove some of the equipment from the UPS. Note that the UPS continues to operate, but may switch to Bypass mode or shut down if the load increases.
  • J
    Jennifer ThomasAug 17, 2025
    Why is the Eaton UPS battery mode LED on?
    • R
      rlewisAug 18, 2025
      The Battery mode LED is On with 1 beep every 10 seconds because a utility failure has occurred, and the UPS is now in Battery mode. The UPS is using battery power to keep your equipment running. You should prepare your equipment for shutdown.
  • W
    wkempAug 21, 2025
    What to do if my Eaton 9SX2000I doesn't start?
    • L
      Lisa SmithAug 21, 2025
      If the Eaton UPS doesn't start, there might be several reasons. First, check the input connections to ensure the input source is correctly connected. Second, ensure that the Remote Power Off (RPO) switch is not active, and the RPO connector is properly connected. If the UPS Status menu displays the 'Remote Power Off' notice, inactivate the RPO input.
  • A
    Angela MoonAug 25, 2025
    What to do if Eaton UPS is overheating?
    • A
      Andrew HintonAug 25, 2025
      If the UPS overtemperature LED is On and it beeps every 3 seconds, it indicates that the UPS internal temperature is too high or a fan has failed. If the UPS transferred to Bypass mode, it will return to normal operation when the temperature drops 5 °C below the warning level. If the condition persists, shut down the UPS. Clear vents and remove any heat sources. Allow the UPS to cool. Ensure the airflow around the UPS is not restricted. Restart the UPS.
  • C
    Claire Ruiz MDAug 28, 2025
    What to do if Eaton 9SX2000I battery fault LED is on?
    • J
      Jaime MartinezAug 28, 2025
      If the Battery fault LED is On and the UPS beeps continuously, it indicates that the battery test failed due to bad or disconnected batteries, or the battery minimum voltage is reached in ABM® cycling mode. Verify that all batteries are properly connected. Start a new battery test.
  • K
    Katherine MurphySep 1, 2025
    Why Eaton 9SX2000I UPS battery low LED is on?
    • J
      Jesse PetersonSep 1, 2025
      The Battery low LED is On and the UPS beeps every 3 seconds because the UPS is in Battery mode and the battery is running low. This warning is approximate, and the actual time to shutdown may vary significantly. Depending on the UPS load and number of Extended Battery Modules (EBMs), the 'Battery Low' warning may occur before the batteries reach 20% capacity.
  • T
    Tyler RussellSep 5, 2025
    How to fix Eaton UPS not providing expected backup time?
    • T
      Timothy WilsonSep 5, 2025
      If the Eaton UPS isn't providing the expected backup time, it could be that the batteries need charging or service. To address this, apply utility power for 48 hours to charge the batteries.
  • L
    levineantonioSep 9, 2025
    What to do if Eaton 9SX2000I UPS no battery LED is on?
    • M
      Michael LopezSep 9, 2025
      If no battery LED is On and the UPS beeps continuously, it means that the batteries are disconnected. Verify that all batteries are properly connected.

Summary

Safety Instructions

Safety Precautions

Safety of Persons

Guidelines for safe handling and servicing of UPS systems and batteries.

Product Safety

Essential safety precautions for installing and operating the UPS equipment.

Additional Safety Measures

Special Precautions

Important safety measures for handling, installation, and maintenance of the UPS.

Installation Guides

EBM Tower Installation

UPS Tower Installation

UPS Rack Installation

EBM Rack Installation

Interfaces and Communication

Control Panel Overview

Description of the UPS graphical LCD control panel and its indicators.

UPS LCD Display

Display and User Settings

Communication Ports

Communication Ports and Cards

Information on RS232, USB ports, and installation of optional communication cards.

Remote Control Functions

Remote Control and Input Signals

Configuration and use of remote control functions and programmable signal inputs.

UPS Operation

Start-up and Normal Operation

Steps for starting the UPS, normal operation, and initiating battery power.

Starting the UPS on Battery Power

Procedure for initiating UPS operation using battery power.

UPS Operating Modes

UPS Shutdown Procedure

Instructions for safely shutting down the UPS system.

Bypass and Efficiency Settings

Battery Configuration

Battery Settings and Logs

Event and Fault Logs

Battery Replacement

Battery Replacement Guidance

Information on UPS battery lifespan and when replacement is recommended.

Replacing Internal Batteries

Replacing Internal Batteries

Detailed steps for replacing internal batteries in tower and rack UPS models.

Troubleshooting

Typical Alarms and Faults Resolution

Chart to diagnose and resolve common UPS alarms and faults.

Alarm Resolution and Support

Specifications

Eaton 9SX2000I Specifications

General IconGeneral
Power Rating2000 VA / 1800 W
Output Frequency50/60 Hz
Form FactorTower
Frequency Range40-70 Hz
Operating Temperature0 to 40 °C
Storage Temperature-15 to 45 °C
Humidity0-95% non-condensing
Warranty2 years
Output Voltage220/230/240 V
Battery TypeSealed Lead Acid
Runtime at Half Load10 minutes
EfficiencyUp to 95%
Output ReceptaclesIEC C13
CommunicationUSB, RS-232
Input Voltage Range160 - 300 V
TopologyDouble Conversion Online
Typical Recharge Time4 hours to 90% capacity