Instructional Booklet
Page 20 Effective: March 2010
Instructions for Installation, Operation and Maintenance of the
Eaton ATC-600 Automatic Transfer Switch Controller
For more information visit: www.eaton.com IB ATS-1005
5.4 Programmable Features/Setpoints
All ATC-600 programmable features and associated setpoint pos-
sibilities with any required explanations are presented in Table 2.
Remember, only features originally ordered and factory pro-
grammed will appear in the display.
Table 2. Programmable Features/Setpoints.
CAUTION
CHANGING THE SYSTEM NOMINAL VOLTAGE OR FREQUENCY SET-
POINTS WILL AUTOMATICALLY CHANGE ALL THE PICKUP AND
DROPOUT SETTINGS TO NEW DEFAULT VALUES.
PROGRAMMABLE
FEATURE DISPLAY
DISPLAY
EXPLANATION
SETPOINT
RANGE
FACTORY DEFAULT
VALUE MEASURE
TDES Time Delay Engine Start Timer 0 to 120 Seconds 0:03 Minutes: Seconds
TDNE Time Delay Normal to Emergency Timer 0 to 1800 Seconds
0:00 Minutes: Seconds
TDEN Time Delay Emergency to Normal Timer 0 to 1800 Seconds
5:00 Minutes: Seconds
TDEC Time Delay Engine Cool Down Timer 0 to 1800 Seconds
5:00 Minutes: Seconds
NOMF System Nominal Frequency (Hertz) 50 or 60 Hz
3
60 Hertz
NOMV System Nominal Voltage (Volts) 120 to 600 Volts
3
120 Volts
1UVD Source 1 Undervoltage Dropout (Volts) 97 to 50% of Nominal
1
80% Volts
2UVD Source 2 Undervoltage Dropout (Volts) 97 to 50% of Nominal
1
80% Volts
1UVP Source 1 Undervoltage Pickup (Volts) (Dropout +2%) to 99%
1
90% Volts
2UVP Source 2 Undervoltage Pickup (Volts) (Dropout +2%) to 99%
1
90% Volts
1OVD Source 1 Overvoltage Dropout (Volts) 105 to 120%
1
115% Volts
2OVD Source 2 Overvoltage Dropout (Volts) 105 to 120%
1
115% Volts
1OVP Source 1 Overvoltage Pickup (Volts) 103% to (Dropout-2%)
1
110% Volts
2OVP Source 2 Overvoltage Pickup (Volts) 103% to (Dropout-2%)
1
110% Volts
1UFD Source 1 Underfrequency Dropout (Hertz) 90 to 97%
2
94% Hertz
2UFD Source 2 Underfrequency Dropout (Hertz) 90 to 97%
2
94% Hertz
1UFP Source 1 Underfrequency Pickup (Hertz) (Dropout +1 Hz) to 99%
2
96% Hertz
2UFP Source 2 Underfrequency Pickup (Hertz) (Dropout +1 Hz) to 99%
2
96% Hertz
1OFD Source 1 Overfrequency Dropout (Hertz) 103 to 110%
2
106% Hertz
2OFD Source 2 Overfrequency Dropout (Hertz) 103 to 110%
2
106% Hertz
1OFP Source 1 Overfrequency Pickup (Hertz) 101% to (Dropout -1 Hz)
2
104% Hertz
2OFP Source 2 Overfrequency Pickup (Hertz) 101% to (Dropout -1 Hz)
2
104% Hertz
TDN Time Delay Neutral Timer 0 to 120 Seconds
0:00 Minutes: Seconds
TDNLD
Time Delay Neutral Load Decay
0 = Disabled
1 = Enabled
1 -
LDCY Load Decay Voltage
2 to 30% of Nominal Voltage
30 Volts
PRF SRC Preferred Source None
1=Source 1
2=Source 2
1 -
EXER Plant Exerciser Enabled or Disabled 1=Enabled
0= Disabled
1 -
EXLD Load Transfer with Plant Exerciser 1=Enabled
0= Disabled
1 -
PEDAY Plant Exerciser Day of Week 1 to 7
(1= Sunday)
1 Week Day
PEH Plant Exerciser Hour 1 am to 11 pm
1 AM Hour
PREMIN Plant Exerciser Minute 0 to 59 Minutes
0 Minutes
MANTR Re-Transfer Mode 0= Automatic
1= PB Return
0 -
CTDNE Commitment to Transfer in TDNE 0= Not Committed
1= Committed
0 -
TMODE Engine Test With/Without Load Transfer 0= No Load Transfer
1= Load Transfer
2= Disable Test Pushbutton
1 -
TER Engine Test/Plant Exerciser Run Time 0 to 600 Minutes
0:30 Hours: Minutes
TPRE Pre-Transfer Sub-Network
Time Delay
1 to 300 Seconds
0:01 Minutes: Seconds
GENNO Number of Generators
(Single Generator Must Be On Source 2)
0 to 2
1 -