Tap position indication (TPI)
The control has the ability to track the position of the tap-
changer. The TPI function senses the status of the motor 
and neutral light circuits and does not require source (input) 
voltage. The present tap position is stored at FC 12. 
EXAMPLES: “8” at FC 12 indicates 8 raise and “-7” 
indicates 7 lower.
The TPI function is synchronized to the position of the tap-
changer by running the regulator to the neutral position. 
To manually set the present tap position: Access Admin 
security level; access FC 12; use the EDIT key to change to 
the desired value.
The maximum tap position since last reset (upper drag-hand 
value of the present tap position) and its date and time are 
stored at FC 27. The minimum tap position since last reset 
(lower drag hand value of the present tap position) and its 
date and time are stored at FC 28.
The TPI drag hand values and dates/times are reset to the 
present values by the master reset, FC 38, or by resetting 
each of the values individually. The drag hand reset switch 
resets the drag hands of the position indicator only, not TPI. 
All TPI values are stored in non-volatile memory. 
The following conditions could occur if the present tap 
position was manually set incorrectly: 
 
The present tap position value will go to invalid “---” if 
the present tap position is 0 (zero, neutral) but no neutral 
signal is detected. For example, this condition will occur 
if a replacement control with present tap position set to 
“0” is installed on a regulator which is not in the neutral 
position. 
 
If the TPI function detects a successful upward tap 
and the prior value of FC 12 was “16”, or a successful 
downward tap is detected and the prior value of FC 12 
was “–16,” the prior value will be maintained.
The display will show a diagnostic error message upon 
power-up when: (1) the present tap position value prior to 
power-up is “---” (invalid) and the regulator is not in neutral 
position; (2) The present tap position prior to power-up is 
“0” and the regulator is not in the neutral position. [This 
condition will cause the present tap position value to go to 
invalid (“----”)]; and (3) During automatic or manual operation 
the present tap position changes to “0”, but a neutral signal 
is not received. The No Neutral Sync signal is an attention 
signal, not a failure signal.
The TPI will satisfy the diagnostics routine upon power-
up when: (1) The regulator is in neutral and the present 
tap position is “0”; (2) The present tap position is not “0” 
and the regulator is not in neutral, including when the tap 
position is not set correctly; and (3) When the regulator is in 
neutral and the present tap position is not “0” (TPI will self-
correct and reset the tap position).
Source-side voltage
Without a source voltage input, some functions will indicate 
dashes when displayed. There are three methods for 
supplying a source-side voltage to the CL-7 control: Internal 
Differential Potential Transformer (IDPT), source-side PT, or 
source-side voltage calculation.
Differential voltage
The voltage regulator may be designed and ordered with 
an Internal Differential PT (IDPT). The IDPT will be included 
in the schematic on the voltage regulator nameplate and 
labeled Series Winding Potential Transformer. An IDPT 
supplies the voltage difference between the source and 
load bushings of the voltage regulator. This differential 
voltage is then combined with the load voltage to provide 
the source-side voltage. When using an IDPT on an Eaton's 
Cooper Power series voltage regulator, the source voltage 
accuracy is within ± 1%.
As a standard, a second ratio correction transformer (RCT2) 
is not supplied on regulators equipped with an IDPT. The 
control will use the internal PT ratio entered at FC 44 and 
the input voltage from the IDPT to determine the differential 
voltage between the source and the load bushings. The 
setting at FC 146 must be set to Vdiff without RCT2 for this 
configuration. 
If an RCT2 is supplied, the Overall PT Ratio entered at 
FC 44 and the input voltage from the IDPT are used to 
determine the differential voltage. The setting at FC 146 
must be set to Vdiff with RCT2 for this configuration.
Source voltage
A source-side PT may be used to supply a directly 
measured source voltage. When using a source-side PT, the 
user must change Vin PT Configuration, FC 146, from the 
default Vdiff without RCT2 to Vin Mode. Some manufactures 
use a source PT as a standard. Using an external source-
side PT may be desirable if the voltage regulators are in 
a closed-delta configuration. In a closed delta, the source 
voltage and percent regulation will only reflect the true 
system source values if an external source voltage or 
DeltaCalc feature is used. Voltage regulator performance 
is not affected by the difference between metering 
parameters when using an external source PT: the accuracy 
of the source voltage is dependent upon the accuracy of 
the PT. When FC 146 is set to Vin, the control will use the 
Internal P.T. Ratio (FC 44) to determine the measured 
source bushing voltage.
Source-side voltage calculation
The CL-7 control has the ability to calculate the source-side 
voltage without an IDPT or source PT. When this feature 
is turned on at FC 39, the control will use the load voltage 
from the main PT, the regulator type (Type A, Type B, Type 
C or Type D), the tap position, and the internal impedance 
of the regulator to calculate the source-side voltage. This 
calculated source voltage is accurate to within ±1.5%. Only 
the regulator type needs to be programmed into the control; 