Section 7: Advanced control features
Figure 49.  Operation analysis using Metering-PLUS feature
Metering-PLUS feature
The Metering-PLUS feature was designed to allow 
immediate access to basic control information. On the 
CL-7 control, the keypad can be configured to assign Hot-
Key access to the Metering-PLUS displays. The Hot-Key 
assignments are shown on the right side of the control. 
As a default, the CL-7 control is programmed with the 
Metering-PLUS Comp Voltage, Load Voltage, Load Current 
and Tap Position screens being assigned as hot-keys to key 
numbers 1 through 4 respectively. 
Compensated voltage
When the *Comp Voltage key is pressed, the LCD will 
display the following information.
The first line displays a live representation of the 
compensated voltage. The compensated voltage is also 
available at FC 8.
The second line is used to display the in-band compensated 
voltage range. The voltage range is dependent on four 
separate parameters: operating mode, metering power 
direction, set voltage, and bandwidth in the corresponding 
metering power direction.
The third line specifies the range of configurable function 
codes that are used to compute the in-band compensated 
voltage range and the corresponding time delay.
The Out-of-Band High and Out-of-Band Low LEDs are used 
to indicate an out-of-band condition. 
EXAMPLE 1:
 Comp  Voltage  125.0
 Band  119.0-121.0
 Using  Func  1-5
 
Compensated Voltage = 125.0 V
 
Fwd. Set Voltage = 120.0 V
 
Fwd. Bandwidth = 2.0 V
 
Control experiencing forward power flow as indicated by 
reference to FC 1-5.
143
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS   MN225003EN   April 2018
CL-7 Voltage Regulator Control