Explosion-protected, light alloy Ex-d (e) control stations and
distributions, Series: GHG 64
1.2.1.1 Safety switch GHG 64 .. (80 A)
Rated voltage 690 V, 50/60 Hz
Rated current 80 A
Perm. short circuit back-up fuse up to UN 400 V up to UN 500 V up to UN 690 V
100 A/gG 100 A/gG
Switching capacity AC 23 80 A 58 A 20 A
Cable entries (standard version) according to customer specifications
under the approval
T
erminals 2 x 1.5 - 35 mm²
Test torque terminals 2.5 Nm
Weight 3-pole (acc. to specification)
6-pole (acc. to specification)
1.2.1.2 Safety switch GHG 64 .. (250 A)
Rated voltage 690 V, 50/60 Hz
Rated current 250 A
Perm. short circuit back-up fuse up to UN 400 V up to UN 500 V up to UN 690 V
315 A/gG 315 A/gG
Switching capacity AC 23 250 A 250 A 250 A
Cable entries (standard version) according to customer specifications
under the approval
T
erminals M8 x 25
Test torque terminals 22 Nm
Weight 3-pole (acc. to specification)
6-pole (acc. to specification)
Dimension drawing
Enclosure Gr. 80 A
Dimension drawing
Enclosure Gr. 250 A
1
2
3
4
5
6
L1IN L2 L3 PE PE 11 13 PE
11 13 PE
11 13
12 14
12 14
L1OUT L2 L3 12 14
90°
0
I
Wiring diagram
main and safety switch up to 250 A
1
2
3
4
5
6
L1IN L2 L3 PE PE 11 13 PE
11 13 PE
11 13
12
14
12 14
L1OUT L2 L3 12 14
90°
0
I
Wiring diagram
main and safety switch up to 80 A
320
320
357
284295
254
255
934,5
320
320
295
357
284
254
255
634,5